background image

 

Thermostat TOA

 

 

Doc: 70-00-0851A V1.0, 20210716 

© Vector Controls GmbH, Switzerland 

 Page 1 / 10 

Subject to change without notice 

www.vectorcontrols.com 

Thermostat TOA-T101, TOA-T102 

Overview 

The TOA is an electronic thermostat (temperature monitor) for NTC 

temperature sensors with outputs for 230V or 24 V AC/DC actuators. 
If the measured temperature exceeds the temperature limit, the 

thermostat switches off its output. If the temperature returns to within 

the allowed limit, the output is switched back on.  
The thermostat can work for heating or cooling applications.  
The TOA is delivered with a maximum temperature limit of 35°C (95 °F) 

and an allowed limit of 30 °C (86 °F) 
It can be adjusted by the user using the OPA-S operating terminal if 
required. 
Note: The thermostat does not include temperature sensors. These need 
to be ordered separately.  

 

 

Features 

-

 

TOA-T101:  

 

230 VAC or 24 V AC/DC power supply 

 

24 V output 

-

 

TOA-T102:  

 

230 VAC power supply 

 

230 VAC output 

-

 

Adjustable switch on and off temperature limits. 
-20...100 °C (-4...212 °F) adjustment range 

-

 

0.5 °C (1 °F) measuring accuracy 

-

 

Signal LED indicates operating status of Thermostat 

-

 

Temperature can be measured at the device or remotely 

-

 

Easy programming of settings with external control unit 

-

 

Quick copying of predefined settings using a memory device 

 

Applications 

-

 

Ventilation damper control for elevator shafts. 

Control of damper for temperature control in an elevator shaft by opening or closing the motorized dampers 

(with spring return). 

-

 

Frost protection 

Activating a heating device if temperature gets close to freezing.  

 

 

Examples 

Elevator shaft ventilation with TOA-T101: 

 

Elevator shaft ventilation with TOA-T102:

 

 

Product Testing and Certification 

 

Declaration of 

Conformity 

Information on the conformity of our products can be found on our website 

www.vectorcontrols.com 

on the corresponding product page under "Downloads". 

TOA-T101

Motorized damper with spring return

Normally open

M

24 V AC/DC

230 VAC / 24 V AC/DC

N / GND

Open - Auto

Open - Auto

Main switch

Switch machine 

room

Temperature

Sensor

TOA-T102

Motorized damper with spring return

Normally open

M

230 VAC

230 VAC

Open - Auto

Open - Auto

Main switch

Switch machine 

room

Temperature

Sensor

Содержание 40-100242

Страница 1: ...limits 20 100 C 4 212 F adjustment range 0 5 C 1 F measuring accuracy Signal LED indicates operating status of Thermostat Temperature can be measured at the device or remotely Easy programming of set...

Страница 2: ...ty Technical Specifications Power supply Operating voltage TOA T101 230 VAC 10 50 60 Hz 24 VAC 10 50 60 Hz 24 VDC 15 34 VDC TOA T102 230 VAC 10 50 60 Hz Power consumption Min 10 VA Safety extra low vo...

Страница 3: ...sions mm inch Mounting and Installation The Thermostat must be mounted on a dry place Temperature sensor selection Use Vector Controls NTC temperature sensors to achieve maximum monitoring accuracy Di...

Страница 4: ...y 230 VAC 50 60 Hz P3 Input Power supply 24 V AC DC P4 Input Temperature sensor NTC 10k at 25 C P6 Connection for OPA S operation terminal Plug P7 Connection for AEC PM2 memory device Plug J1 Connecto...

Страница 5: ...Power supply 230 VAC 50 60 Hz P4 Input Temperature sensor NTC 10k at 25 C P6 Connection for OPA S operation terminal Plug P7 Connection for AEC PM2 memory device Plug LED Signal LED shows operating st...

Страница 6: ...see picture below 4 Close unused housing cable cut out with the supplied blind insert see picture below 5 Apply operating voltage to TOA and observe signal LED see section Signal LED page 7 The signa...

Страница 7: ...ltage for an OFF ON setting of 20 C 25 C 68 F 77 F Signal LED The signal LED on the top of the housing indicates the operating status of the TOA LED Status Description red Output is off The contact is...

Страница 8: ...T key 5 Confirm the IP SEL display with the RIGHT key The first parameter is displayed 6 Change to the parameter IP 03 with the UP or DOWN keys After pressing the RIGHT key the parameter Switching OFF...

Страница 9: ...s set to 7 9 Remove the AEC PM2 memory device and the OPA S operator interface and close the TOA housing see section Connecting the TOA and putting it into operation page 6 Copy parameters to other TO...

Страница 10: ...ector Controls GmbH Switzerland Page 10 10 Subject to change without notice www vectorcontrols com Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland...

Отзывы: