Copy TOA parameters 

It is possible to load TOA parameters to the memory device AEC-PM2 and copy them to other TOA 
devices. 

 

Loading memory device 

1.

 

Remove the upper part of the TOA housing (see section "Connecting the TOA and putting it 

into operation", page 6). 

2.

 

Insert the AEC-PM2 memory device into the TOA connector 

P7

. Ensure correct polarity (see 

section "Wiring and Connection", page 4)! 

3.

 

Connect the OPA-S operating device to the TOA connector 

P6

 (see section "Wiring and Connection", page 4). 

The measured temperature is displayed. 

4.

 

Press the "UP" and "DOWN" keys simultaneously for at least 3 seconds and wait until "Code" is displayed. 

5.

 

Use the "UP" or "DOWN" keys to set the password "0009" and confirm with the "RIGHT" key. 

6.

 

Confirm the "IP SEL" display with the "RIGHT" key. The first parameter will be displayed. 

7.

 

Use the "UP" or "DOWN" keys to switch to the "IP 05" parameter. After pressing the "RIGHT" key, use the "UP" 

or "DOWN" keys to set the parameter to "1". Confirm the setting with the "RIGHT" key. 

8.

 

After pressing the left "ON/OFF" key twice, the parameters are copied from the TOA to the AEC-PM2. 
The red "Data" LED of the AEC-PM2 lights up for 5 seconds after successful copying and parameter "IP 05" is set 

to 0. If copying has failed, the red "Data" LED flashes for 5 seconds and parameter "IP 05" is set to 7. 

9.

 

Remove the AEC-PM2 memory device and the OPA-S operator interface and close the TOA housing (see section 

"Connecting the TOA and putting it into operation", page 6). 

Copy parameters to other TOA devices 

1.

 

Remove the upper part of the TOA housing (see section Connecting the TOA and putting it into operation, page 

5). 

2.

 

Insert the AEC-PM2 memory device into the TOA connector P7. Ensure correct polarity (see section "Wiring and 

Connection", page 4)! 

3.

 

After pressing the "Copy" key on the AEC-PM2, the parameters are copied from the AEC-PM2 to the TOA. 

The red "Data" LED of the AEC-PM2 lights up for 5 seconds after a successful copy process. If copying has failed, 

the red "Data" LED flashes for 5 seconds. 

4.

 

Remove the AEC-PM2 memory device and close the TOA housing (see section "Connecting the TOA and putting it 

into operation", page 6). 

Signal LED on the AEC-PM2 memory device 

LED (red) 

Status 

Description 

lights up 

successful 

Copying of parameters successfully completed. LED lights up for 5 seconds. 

flashes 

error 

Error while copying the parameters. LED flashes for 5 seconds. 

 

 

Additional Information 

Conventions 

The following display conventions apply to this document: 
 

 

Danger 

Indicates a hazard with a high degree of risk. Failure to observe this warning may result in immediate danger of 

serious injury or death. 

 

 

Important 

Failure to comply with these warnings can result in equipment damage. 

 

 

Information 

Further information, important operating instructions, other details. 

 

 

Reference to another document or other text passages. 

 

Used abbreviations 

Abbreviation  Meaning 

NTC 

Negative Temperature Coefficient 

 

 

 

D

at

a

Co

p

y

AEC-PM2

1

Содержание 40-100242

Страница 1: ...limits 20 100 C 4 212 F adjustment range 0 5 C 1 F measuring accuracy Signal LED indicates operating status of Thermostat Temperature can be measured at the device or remotely Easy programming of set...

Страница 2: ...ty Technical Specifications Power supply Operating voltage TOA T101 230 VAC 10 50 60 Hz 24 VAC 10 50 60 Hz 24 VDC 15 34 VDC TOA T102 230 VAC 10 50 60 Hz Power consumption Min 10 VA Safety extra low vo...

Страница 3: ...sions mm inch Mounting and Installation The Thermostat must be mounted on a dry place Temperature sensor selection Use Vector Controls NTC temperature sensors to achieve maximum monitoring accuracy Di...

Страница 4: ...y 230 VAC 50 60 Hz P3 Input Power supply 24 V AC DC P4 Input Temperature sensor NTC 10k at 25 C P6 Connection for OPA S operation terminal Plug P7 Connection for AEC PM2 memory device Plug J1 Connecto...

Страница 5: ...Power supply 230 VAC 50 60 Hz P4 Input Temperature sensor NTC 10k at 25 C P6 Connection for OPA S operation terminal Plug P7 Connection for AEC PM2 memory device Plug LED Signal LED shows operating st...

Страница 6: ...see picture below 4 Close unused housing cable cut out with the supplied blind insert see picture below 5 Apply operating voltage to TOA and observe signal LED see section Signal LED page 7 The signa...

Страница 7: ...ltage for an OFF ON setting of 20 C 25 C 68 F 77 F Signal LED The signal LED on the top of the housing indicates the operating status of the TOA LED Status Description red Output is off The contact is...

Страница 8: ...T key 5 Confirm the IP SEL display with the RIGHT key The first parameter is displayed 6 Change to the parameter IP 03 with the UP or DOWN keys After pressing the RIGHT key the parameter Switching OFF...

Страница 9: ...s set to 7 9 Remove the AEC PM2 memory device and the OPA S operator interface and close the TOA housing see section Connecting the TOA and putting it into operation page 6 Copy parameters to other TO...

Страница 10: ...ector Controls GmbH Switzerland Page 10 10 Subject to change without notice www vectorcontrols com Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland...

Отзывы: