background image

15

AC35

AC35-E

351

0E

3520E/3525E

351

0E/3515E

40

0V3~

PLSB1

40

0V3~

Actuator

230V~ 

Transformer

230V

20

0V

170V

145V

120V

10

0V

N

Blac

k

Blac

k

Gre

y

Blue

Blue

White

White

C2

C1

ROOM

Internal 

sensor

Motor

protection

°C

°C

°C

Transformer

230V

20

0V

170V

14

5V

120V

10

0V

N

Yellow

Orange

Re

d

Brown

Blac

k

Green

Blue

N

N

3515E

°C

°C

°C

°C

3525E

3520E

230V~

Содержание AC35

Страница 1: ...AC35 Art nr 172786 01 GB Installation and maintenance instruction for air curtains IMPORTANT Read these instructions before the product is installed and used Save the instructions for future use 2 ...

Страница 2: ...supplied with electrical heating or hot water heating AC35 is intended for en trances and smaller doors up to 3 5 metres in height Protection class for units with electrical heating IP20 Protection class for units with water heating IP21 Operation Air is drawn in at the top rear of the unit and blown out downwards outwards so that it shields the door ope ning and minimizes heat loss To achieve the...

Страница 3: ...the air curtain with an integrated control card see fig 2 PLS is supplied pre programmed with quick fit connec tions Modular cables are connected to the control board See manual for PLS Unit with water heating Connected via the built in PLS control board with 2 m cord and plug Unit with electrical heating The installation is made on the top of the unit horizon tal or on the reverse vertical Contro...

Страница 4: ... and subsequent water leakage during connection to water supply pipe work Adjustment of the air curtain and air flow The direction and speed of the air flow should be ad justed considering the load on the opening Pressure forces affect the air stream and make it bend inwards into the premises when the premises are heated and the outdoor air is cold The air stream should therefore be directed outwa...

Страница 5: ...trical coil to cool 3 Determine the cause of overheating and rectify the fault 4 Connect the air curtain again All motors are equipped with an integral thermal safety cut out This will operate stopping the air curtain should the motor temperature rise too high The cut out will automatically reset when the motor temperature has returned to within the motor s operating limits Temperature control Tem...

Страница 6: ... incoming water is heated enough If the fault cannot be rectified please contact a qualified service technician Residual current circuit breaker E When the installation is protected by means of a residual current circuit breaker which trips when the appliance is connected this may be due to moisture in the heating element When an appliance containing a heater element has not been used for a long p...

Страница 7: ...L3525 8 M8 DN20 3 4 outside thread 160 A 43 205 92 364 40 PLS 2 m 2 5 m L1 528 275 40 23 L mm A mm AC35 10 1073 72 AC35 15 1583 72 AC35 20 2073 74 AC35 25 2583 71 L1 mm AC35 15 1589 AC35 20 2079 AC35 25 2589 AC35 10 35 15 4 M8 AC35 20 6 M8 AC35 25 8 M8 ...

Страница 8: ...e front is blocked in open position with the front hatch hook Fig 2 Control card PLS is integrated in the air curtain at delivery Fig 1B When the front has been removed it is important to be sure it is firmly seated in the front locks again 100 Fig 3 Minimum distance ...

Страница 9: ...9 AC35 A B A 160 L B 160 875 875 A B 160 770 745 745 Fig 5 M8 holes for mounting Fig 4 B A 3 4 Filling the water coil L mm AC35 10 750 AC35 15 1260 A B AC35 205 92 1 2 ...

Страница 10: ...10 AC35 Fig 6 See separate manual for PA34WB AC35 PA34WB 20 mm 79 19 120 11 40 PA34WB AC35 W 15 2 pcs AC35 W 20 3 pcs AC35 W 30 4 pcs A B D E C F ...

Страница 11: ...11 AC35 PL3JK PA34WS PA34CB PA34TR PA34CB Fig 7 PA34TR PA34CB See separate manual for PA34TR Fig 8 PA34WS PA34CB See separate manual for PA34WS ...

Страница 12: ...12 AC35 Note The top of the air curtain must be secured in the wall or ceiling Fig 9 See separate manual for PL3JK PL3JK ...

Страница 13: ... m PA34WS20 Wire suspension kit for 2 meter units Units 6 pcs AC35 20 Fig 8 PA34WS30 Wire suspension kit for 2 5 meter units Units 8 pcs AC35 25 Fig 8 PA34TR15 Threaded rods for 1 and 1 5 meter unit Units 4 pcs AC35 10 15 Fig 7 Threaded rods for ceiling moun ting Used with ceiling mounting brackets PA34CB Length 1 m PA34TR20 Threaded rods for 2 meter unit Units 6 pcs AC35 20 Fig 7 PA34TR30 Threade...

Страница 14: ... unit PLSDC door switch and 2 modular cables with RJ12 quick connects 1 pc 3 m 1 pc 5 m IP30 PLSRTX External room temperature sensor 70x33x23 mm SIRECJ4 RJ11 coupler 4 4 Used to join together two RJ11 or RJ12 connec tors SIRECJ6 RJ12 coupler 6 6 SIRECC403 RJ11 modular cable 4 4 Length 3 m SIRECC405 Length 5 m SIRECC410 Length 10 m SIRECC415 Length 15 m SIRECC603 RJ12 modular cable 6 6 Length 3 m S...

Страница 15: ...ctuator 230V Transformer 230V 200V 170V 145V 120V 100V N Black Black Grey Blue Blue White White C2 C1 ROOM Internal sensor Motor protection C C C Transformer 230V 200V 170V 145V 120V 100V N Yellow Orange Red Brown Black Green Blue N N 3515E C C C C 3525E 3520E 230V ...

Страница 16: ...ansformer 230V 200V 170V 145V 120V 100V N Black Blue White White Supply 230V C2 C1 ROOM Internal sensor Motor protection Transformer 230V 200V 170V 145V 120V 100V N Yellow Orange Red Brown Black Green Blue 3510W C C C 3515W C C C C 3225W 3520W ...

Страница 17: ...ent see manuals for PLS 230V 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY PLSB1 PLSB1 PLSRTX optional PLSUB1 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY PLSB1 PLSRTX optional PLSUB1 ...

Страница 18: ...18 AC35 PLS Basic AC35 W C C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY 230V PLSB1 SD230 PLSRTX optional PLSUB1 ...

Страница 19: ...t see manuals for PLS C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY 230V 230V 230V PLSB1 SD230 SD230 SD230 PLSB1 PLSB1 PLSUB1 PLSRTX optional ...

Страница 20: ...tt 556138 3166 VAT no SE556138316601 Postal Cheque Service 48 51 08 5 Bank Transfer 926 0365 Fax Int 46 451 410 80 E mail veab veab com Phone Int 46 451 485 00 Website www veab com NB We reserve us from typographical errors and the right to make changes and improvements to the contents of this manual without prior notice AC35 20 ...

Отзывы: