ALFA(NET) 79 PI 

0/100%RH

 

 

1

 

Function 

The  ALFA(NET)  79  PI  is  a  Panel  mount  hygrostat-unit.  The  hygrostat  has  three  relay  outputs 
selectable  for  function  humidify,  dehumidify  or  alarm.  And  an  PI-output  0-10Vdc  for  function 
humidify  or  dehumidify.  The  relative  humidity  is  being  measured  by  a  RH-sensor  (Relative 
Humidity) with an 0-1Vdc = 0-100%RH signal output. 

The ALFANET 79 PI is provided with a RS-485 network connection, with which it can be readout or 
set on the ALFANET. 

2

 

Installation 

On the connection diagram of the ALFA(NET) 79 PI is shown how the sensor, power supply, relays, 
PI-output and optional network are to be connected. After connecting the ALFA(NET)  79 PI to the 
power supply, a self-test function is started. As this test is finished, the measured relative humidity 
appears in the display. 

3

 

Control 

The ALFA(NET) 79 PI hygrostat can be controlled by four pushbuttons on the front. These keys are;  

8

 

SET 

 

- view / change set value and reset alarm. 

∏ 

UP 

 

- increase set value. 

π 

DOWN   

- decrease set value. 

%RH  STATUS 

- hidden relays status key. 

 

 

Содержание ALFANET 79 PI

Страница 1: ...e Humidity with an 0 1Vdc 0 100 RH signal output The ALFANET 79 PI is provided with a RS 485 network connection with which it can be readout or set on the ALFANET 2 Installation On the connection diagram of the ALFA NET 79 PI is shown how the sensor power supply relays PI output and optional network are to be connected After connecting the ALFA NET 79 PI to the power supply a self test function is...

Страница 2: ... of the relays Each display segment shows the status of the relay output showing 0 off and 1 on The code 110 means relay 1 and 2 are on and relay 3 is off 7 Adjustment sensor The RH sensor can be adjusted by using the Offset RH Sensor parameter 05 Indicates the Sensor e g 2 RH too much the Offset RH Sensor parameter has to be decreased with 2 RH 8 Error messages In the display of the ALFA NET 79 P...

Страница 3: ... cut out 28 x 70 mm H x W front mounting Maximum voltage of the Analog output is power supply 3 volts Provided with memory protection during power failure Connection with screw terminals Equipped with senor failure detection Special versions are on request available 10 Setting internal parameters Next to the adjustment of the setpoint internal settings can be made like differential sensor offset s...

Страница 4: ...ay 2 15 15 RH 0 14 Switching differential relay 3 1 15 RH 1 15 Switching offset relay 3 15 15 RH 0 20 Minimum adjustable setpoint 0 100 RH 0 21 Maximum adjustable setpoint 0 100 RH 100 30 Alarm type 0 None 1 Absolute 2 Relative 0 2 1 31 Minimum alarm setpoint 0 100 RH 0 32 Maximum alarm setpoint 0 100 RH 100 33 Time delay minimum alarm 0 99 Minutes 0 34 Time delay maximum alarm 0 99 Minutes 0 35 F...

Страница 5: ...ALFA NET 79 PI 0 100 RH Document no 170986 version 1 0 Pagina 5 van 8 11 Function diagram ...

Страница 6: ...ALFA NET 79 PI 0 100 RH Document no 170986 version 1 0 Pagina 6 van 8 12 Connections ...

Страница 7: ...ALFA NET 79 PI 0 100 RH Document no 170986 version 1 0 Pagina 7 van 8 13 Dimensions ...

Страница 8: ...0 RH Document no 170986 version 1 0 Pagina 8 van 8 14 Address VDH Products B V Tel 31 0 50 30 28 900 Productieweg 1 Fax 31 0 50 30 28 980 9301 ZS Roden Email info vdhproducts nl The Netherlands Internet www vdhproducts nl ...

Отзывы: