User manual
ALFA 71 MODulation
Thermostat.

VDH doc. 052939

Version: v1.0

Date: 03-10-2005

Software: ALFA71MOD

File: DO052939.WPD

Range: -50/+50,0

C

* Installation.

On the top side of the 

ALFA 71 MOD

 is shown how the sensors, power supply, relays and 0..10Vdc

PI output has to be connected.
After connecting the 

ALFA 71 MOD

 to the power supply, a self test function is started. As this test is

finished the measured temperature appears in the display.

* Control.

The 

ALFA 71 MOD

 thermostat can be controlled by four pushbuttons on the front. These keys are:

SET

- view / change the setpoint.

UP

- increase the setpoint.

DOWN

- decrease the setpoint.

C

- hidden push button above the 

SET

 key and behind 

C

 symbol.

* Viewing setpoint.

By pushing the 

SET

 key the setpoint appears in the display. The decimal point of the last display

starts blinking. A few seconds after releasing the 

SET

 key the setpoint disappears and the

measured temperature is shown again in the display.

* Changing setpoint.

Push the 

SET

 key and the setpoint appears in the display. Release the 

SET

 key. Now push the 

SET

key again together with the 

UP

 or 

DOWN

 keys to change the setpoint. A few seconds after

releasing the keys the measured temperature shows again in the display.

* Status of the Relays.

By pushing the hidden 

C

 key the display shows the status of the relays. Each display segment

shows the status of the relay output, showing 0=off and 1=on. The code 110 means relay 1 and 2
are on and relay 3 is off.

* Readout valve position.

By pushing the 

UP

 key the display shows the current valve position.

* Setting internal parameters.

Next to the adjustment of the setpoint, internal settings can be made like differential, sensor-offset,
setpoint range and the functions of the thermostat.
Push the 

DOWN

 key more than 10 seconds, to enter the 'Internal Programming Menu'. In the left

display the upper and lower segment are blinking. Over the 

UP

 and 

DOWN

 keys the required

parameter can be selected (see table for the parameters).
If the required parameter is selected, the value can be read-out by pushing the 

SET

 key. Pushing

the 

UP

 or 

DOWN

 key to change the value of this parameter.

If after 20 seconds no key is pushed, the 

ALFA 71 MOD

 changes to the normal operation mode.

Содержание ALFA 71 MOD

Страница 1: ...rs in the display Release the SET key Now push the SET key again together with the UP or DOWN keys to change the setpoint A few seconds after releasing the keys the measured temperature shows again in the display Status of the Relays By pushing the hidden C key the display shows the status of the relays Each display segment shows the status of the relay output showing 0 off and 1 on The code 110 m...

Страница 2: ...ion for a open circuit sensor Reset Alarm When a error messages appears it can be resetted by pushing the SET key The function of this key depends on parameter P37 Technical details Type ALFA 71 MOD Thermostat Range 50 50 0 C above 10 C display per 0 1 C Supply 12Vac 50 60Hz 5 10 Display 3 digit 7 segment display Relays Ry1 Open SPST NO 250V 8A cos 1 of 250V 5A cos 0 4 Ry2 Close SPST NO 250V 8A co...

Страница 3: ...m alarm setpoint Maximum alarm setpoint Time delay minimum alarm Time delay maximum alarm Relay function alarm relay Reset alarm relay after recovering alarm Reset alarm relay after manual reset 0 None 1 Absolute 2 Relative 50 0 50 0 C 50 0 50 0 C 0 99 min 0 99 min 0 Watch alarm 1 Control alarm 0 No 1 Yes 0 No 1 Yes 1 50 50 0 0 0 0 0 40 41 Start up delay after power failure Forced relay function a...

Страница 4: ...4 Dimensions Connections Address VDH Products BV Tel 31 0 50 30 28 900 Produktieweg 1 Fax 31 0 50 30 28 980 9301 ZS Roden Email info vdhproducts nl The Netherlands Internet www vdhproducts nl ...

Отзывы: