background image

Mar 07

Ventilation Control Products                                               Phone:  +46-(0)31-811666                                            E-mail:     [email protected]
Sågmästaregatan 1D                                                        Fax:      +46-(0)31-812766                                           Web:        www.vcp.se
416 80 Göteborg, Sweden

Air Differential Pressure Transmitters
with 0-10 Vdc or 4-20 mA Output

984M-
series

Features

• 

Selectable output via jumper

   0-10 Vdc or 4-20 mA output, 3-wire
   with power supply 24 Vac/dc

• 

4-20 mA output, 2-wire

  with power supply 24 Vdc

• 

LED display as option on the 3-wire version

 2 adjoining pressure ranges in one unit,

   pressure ranges selectable via jumper

 Pressure ranges

   from 0-100 Pa up to 0-250 kPa

 Response time 100 ms and 1 s

  selectable via jumper

Technical data

Pressure medium

Air and non-aggressive gases

Linearity and
hysteresis error

< ± 1 % of FS

Working temperature

0 to +50 °C

Storage temperature

-10 to +70 °C

Long-term stability, typ.

< ± 0.5 % to 2.5% of FS / year
(depending on pressure range)

Repetition accuracy

< ± 0.2 % of FS

Position dependence

< ± 0.02 % of FS / g

Humidity

0 to 95 % rel, non-condensing

Response time

100 ms or 1 s
(jumper selectable)

Maximum load

< 500 ohm

Process connection

6 mm hose pipe

Electrical connection

Screw terminal block for wire
up to 1.5 mm2

Mounting

Screw mounting with
serrated screws

Housing material

Housing with process
connection P2 made of ABS,
mounting part with process
connection P1 made of POM

Housing dimensions

approx. Ø 85 x 58 mm

Weight approx.

approx. 130 g

Protection category
to EN60529

IP54

Cable conduit for
protection cap

M20 x 1.5 made of Polyamide

Standards / Conformance

EN60770, EN61326

Display, optional

Red LED display, 3.5 digits
(only on 984M.3x3314)

984M without LED display

984M with LED display

984M are supplied with duct fixing kit,
packed together in a carton

Description

The differential pressure transmitters of the 984M series are
used for measuring differential pressure, positive pressure
and vacuum.

Selection of output signal

The output signal of the 3-wire version is configurable.The
factory setting is for a 0-10 Volt output signal, but this can be
changed to 4-20 mA by removing the jumper. The 2-wire
version is only available with a 4-20 mA output signal.

Selection of pressure range

To adapt best for the application the transmitter can be
selected between two adjoining pressure ranges. Factory
setting is for the most sensitve range, by opening of a
jumpered bridge the less sensitive range is activated.

Selection of response time

The response time of the output signal can be selected by a
jumpered bridge. Factory setting is for a slow response time
(1 s), which dampens short pressure peaks. To work with a
fast response time (100ms) this bridge needs to be replaced.

Easy offset calibration

The output signal can be calibrated to zero by pressing the
M key (pressure transmitter must be depressurised).

Switching output 

(only for the 3-wire version)

As well as an analogue output signal, the differential pressure
transmitter contains an adjustable transistor switching output
with a maximum switching capacity of 35 Vdc/100 mA.

Measuring method

Piezoresistive pressure transducer

Mounting position

They can be mounted in any position. Due to the
selfcompensating piezoresistive pressure transducer any
possible mounting error is eliminated.

Отзывы: