INSTALLATION
Series 590
34/56
Edition 2013-05-13
298292EB
4.5.7
Setup commands
Setup function
Command
Acknowledgement
(within 10ms after reception of command)
Description
ACCESS MODE
Set
[c:01][xx][CR][LF]
[c:01][CR][LF]
data length: 2 characters
xx
00
= local operation (service port)
01
= remote operation, change to local enabled
02
= locked remote operation, change to local not possible via service port
This function selects the access authorization to the valve. To read access mode use
inquiry command DEVICE STATUS.
Pay attention:
Local operation is only possible when either ‘Control View’ or ‘Control
Performance Analyzer’ software is running. When communication to service port is
interrupted the valve will automatically change to remote operation.
INTERFACE
CONFIGURATION
Set
[s:20][abcdefgh][CR][LF]
[s:20][CR][LF]
Get
[i:20][CR][LF]
[i:20][abcdefgh][CR][LF]
data length 8 characters
a
baud rate:
0
= 600,
1
= 1200k,
2
= 2400,
3
= 4800,
4
= 9600
5
= 19.2k,
6
= 38.4k,
7
= 57.6k,
8
= 115.2k
b
parity bit:
0
= even,
1
= odd,
2
= mark,
3
= space,
4
= no
c
data length:
0
= 7 bit,
1
= 8 bit
d
number of stop bits:
0
= 1,
1
= 2
e
0
(reserved, do not change)
f
digital input OPEN VALVE:
0
= not inverted,
1
= inverted,
2
= disabled
g
digital input CLOSE VALVE:
0
= not inverted,
1
= inverted,
2
= disabled
h
0
(reserved, do not change)
This function does the RS232 and digital input configuration.
Pay attention:
Digital outputs are always enabled.
Table 4-10
Setup function
Command
Acknowledgement
(within 10ms after reception of command)
Description
RANGE
CONFIGURATION
Set
[s:21][abcdefgh][CR][LF]
[s:21][CR][LF]
Get
[i:21][CR][LF]
[i:21][abcdefgh][CR][LF]
data length 8 characters
a
range for POSITION:
0
= 0
– 1’000,
1
= 0
– 10’000,
2
= 0
– 100’000
bcdefgh
upper value for PRESSURE and SENSOR READING:
1000
...
1000000
e.g. 0010000 -> pressure range 0
– 10’000
This function defines the communication range between the valve and the host computer
for POSITION, PRESSURE and SENSOR READING.
Pay attention:
In case ZERO has been performed, gauge offset for PRESSURE and
SENSOR READING is compensated.
Table 4-11