Värmebaronen Vedolux 55
Operation
Starting the boiler from cold:
• Switch the main switch on. The green field must be
visible.
• 'FAN STOP' thermostat set to 248°F. The thermostat
detects the flue gas temperature.
• Press in 'FAN START'. The time relay operates and the
fan starts.
When the set time of the time relay, 30 minutes, has
elapsed, its contact switches and the charging pump
for the accumulator system will be controlled by the
thermostat.
When the wood has been burned up and the flue gas
temperature has fallen below the set temperature,
the fan and the charging pump will stop.
If the boiler temperature exceeds 212-220°F, the
overheating protection will be triggered. The fan stops
and the charging pump remains in operation.
'ALARM' lights up to indicate that the overheating
protection has been triggered. The overheating
protection is reset by pressing 'RESET' on the control
panel. It is not possible to reset the system until the
boiler temperature has fallen below 200°F. An operating
thermostat limits the boiler's maximum working
temperature.
Electrical connection
The installation must be carried out according to
existing rules and standards under the supervision of
a qualified electrician.
The boiler is connected to the fixed installation with
rubber cable via an all-pole main breaker with at least
0.12 in breaking distance.
The electrical connections are on the rear of the boiler in
the form of three quick connectors:
15. Mains connection, 115 V~, cable is supplied.
16. Fan.
17. Charging pump for the accumulator system.
15. Power supply connection.
a. cable part, sleeve.
b. chassis part, pin.
16. Fan connection.
a. cable part, pin.
b. chassis, sleeve.
17. Connection for charging pump for accumulator system.
a. cable part, pin.
b. chassis, sleeve.
18. Terminal block, internal earth connections.
20. Main power switch.
93°C
25
15a
16a
17a
18
20
21
22
24
26
15b
17b
16b
45
BROWN
BLUE
YELLOW/
FAN
POWER
SUPPLY
115 V~
ALARMS
GREEN
CIRCULATION PUMP
Any intervention in the boiler's electrical
equipment that requires tools must be
carried out under the supervision of a
qualified electrician.
21. Thermostat for fan and charging pump.
22. Fan start when the boiler is cold.
24. Time relay, power off delay.
25. Overheating protection.
26. Indication, overheating
protection triggered.
45. Operating thermostat 200°F.
If the boiler is connected to an emergency power
unit, this must produce a pure sine wave. Otherwise,
the boiler's electrical components may be damaged.
15
16
17
Incoming
Fan
Circulation pump
BLUE
YELLOW/
GREEN
BLACK
BLACK
YELLOW/
GREEN
BLUE
200°F 230°F
Содержание Vedolux 55
Страница 1: ...13 0 9 11 T H L n o x x x x r e v 0 Installation and maintenance Vedolux 55...
Страница 2: ...2 V rmebaronen Vedolux 55...
Страница 10: ...10 V rmebaronen Vedolux 55...
Страница 23: ......