Installation
11
Värmebaronen Vedolux 55
Installation must take place according to
existing regulations and standards.
• The boiler must be placed indoors in a boiler
room designed to meet the existing standard.
• The installation site must withstand the
weight of the boiler, the accumulator tank and
any chimney.
The boiler may be loaded with maximum
220 lb of the chimney's weight vertically
downwards.
• There must be a fresh air intake. Any
mechanical ventilation in the room must not
create any negative pressure that disturbs
the operation of the boiler. The boiler room's
fresh air intake must have an area at least
as large as that of the chimney and it must
be designed so that it cannot be closed by
mistake.
• The existing standards for minimum distance
to combustible material must be met.
The minimum distance for removing the flue
gas fan = minimum 11 in free space behind
the flue gas fan.
Ensure that the provisions for sweeping meet
the existing regulations.
• Adjust the foot bolts so that the boiler is
horizontal.
• The flue pipe must be connected according to
existing standards.
It is important for all connection points and
flues not to leak dust and gas.
If the boiler is connected higher up the
chimney than a previous boiler was
connected, the lower, inactive part must be
filled.
• The boiler must be connected to an open or
closed expansion system.
• The boiler must be connected to an
accumulator system. The installation must
have accumulator control.
• A temperature limiter, thermal valve (STW),
must be fitted.
• No work must take place on the boiler's cover
plates as it can damage the boiler's electrical
equipment.
• The boiler is not designed for oxygenated
water. Hard, calcareous water is not suitable
in a plumbing and heating context.
If you have your own well, the water quality
must be checked so that it does not cause
damage. Copper in the pipes must not be
subjected to abnormally aggressive water.
A water analysis will give you the necessary
information. If the water quality is poor,
a water filter must be installed.
• The turbulators and the draught damper can
be used to adjust the flue gas temperature if
there is a risk of condensation in the chimney.
• A chimney-sweep must be contacted before a
different type of fuel is used.
• Contact the local authority regarding
restrictions on burning solid fuel in a densely
built-up area.