Värmebaronen MP4 G2 / MP6 G2
area
std
16. --
The boiler regulates for a fixed boiler temperature/flow temperature.
16.
1
UTK: Alternative temperature, adjustment.
Which room temperature change should the external input give
Alternative temperature adjustment – Setting (decrease/increase)
Alternative temperature – -20– +5°C, Setting
See "8 - Outdoor temperature sensor and 9 - Alternative temperature / External
blocking in "Electrical installation".
Open input activates the function. Can be used for night-time reduction, holiday
mode or similar, see “Electrical installation”; “Alternative temperature”.
Function without installed room unit: Shifts, parallel displacement, UTK curve level
with a configurable number of stages. This corresponds to a change in the room
temperature by the approximate corresponding number of degrees.
-20 – +5
-5
17. --
Room unit not connected, UTK function not selected, boiler regulates for constant
boiler temperature.
17.
0
Room unit not activated, see "Service level" row 17.
UTK is activated in the "Service Level" menu row 12.
0: does not exist
0
17.
1
Room unit is available, and UTK is activated in the menu "Service level" row 12.
1: available
18.
0
Selection of whether the buzzer should sound or be silent in the event of an alarm. 0: Silent
1
18.
!
Selection of whether the buzzer should sound or be silent in the event of an alarm. 1: Summer
19.
0
Enter 21, for access to “Advanced service level” menu.
Menu - Service Level
Delivery setting