Värmebaronen MP4 G2 / MP6 G2
Menu-User Level
Delivery setting
Heating curve
Use the heating system's dimensioned flow tempera-
ture as the initial value. If the value is not known, gen-
eral values are used. If the room is not at the desired
temperature, additional adjustment is needed. Wait at
least one day between adjustments so that tempera-
tures have time to stabilise.
Dimensioned values, select a curve that gives the
desired flow temperature.
Unknown values - Underfloor heating system, choose
a curve that gives a flow temperature of 40°C for
wooden floors and 30°C for concrete slabs on the
coldest day.
Unknown values - Radiator system, select a curve
that gives a flow temperature of 55°C for a low
temperature system on the "coldest day" and a flow
temperature of 70°C for a high temperature system.
The 'coldest day' is the lowest temperature that
normally occurs in the location.
Adjustment of basic setting
For low temperatures, select a higher level. An in-
crease in the room temperature can be limited by the
thermostats for the radiators or underfloor heating.
For high temperatures, select a lower level.
If the room is not at the desired temperature, ad-
ditional adjustment is needed. Wait at least one day
between adjustments so that temperatures have time
to stabilise.
area
std
4.10
Display of current outdoor temperature, requires that the outdoor temperature sensor
is connected.
Display
4.--
UTK function not selected and the outdoor temperature sensor is not connected.
5.20
Display of the current room temperature.
UTK should be activated and a room unit connected/activated.
See room unit in menu "Service level" row 17
Display
5.--
Fixed boiler temperature regulation is selected.
6.20
Set temperature on the room unit.
UTK should be activated and a room unit activated/connected.
The set temperature is also affected by "Alternative temperature", see menu
"Service level" row 16.
Display
6.--
Fixed boiler temperature regulation is selected.
7.20
Setting the outside temperature for pump stop.
Temperature above the set value puts the boiler on standby.
UTK function must be activated.
If "Alternative Temperature" is used, this area changes.
15 –25°C
17°C
7.--
Fixed boiler temperature regulation is selected.
8. 0
ECO function disabled.
0:
no ECO
function
0
8. 1
ECO function activated. Boiler put on standby. The circulation pump is switched off,
so that it does not get stuck, it will be run for a few minutes every two days.
If necessary, the boiler will start in order to maintain a boiler temperature of
approximately 10°C if external limitation allows.
1:
ECO -
function