Värmebaronen MP4 G2 / MP6 G2
Menu - User Level
User level, rows 1- 8.
area
std
30
Display current boiler temperature.
0 – 60°C
1.35
Display estimated boiler temperature when UTK function is selected, delivery setting.
Display and setting of the desired boiler temperature when the boiler should have a constant
boiler temperature.
Function selection is made in the menu "Service level" row 12.
10 – 60°C
25
2.20
Level heat curve, UTK, parallel displacement of the heat curve, setting
Adjustment will be added to the calculated boiler temperature, see row 1.
5– 30
15
2.--
UTK function switched off, see “Service Level” row 12.
3.38
Slope heating curve, UTK, higher value gives higher boiler temperature when cold outside.
21 – 60
25
3.--
UTK function switched off, see menu “Service Level” row 12.
The boiler temperature is calculated according to the current outdoor temperature, the heat curve set-
tings for level and slope, and possibly the room temperature and alternative temperature.
The boiler temperature can be min/max limited.
The diagram shows the heat curves
30
,
40
and
50
at Level =
20
.
Curve
30
strives for a boiler temperature of 30°C at ±0°C outdoor temperature. The corresponding
curves
40
and
50
are 40 and 50 ° C respectively.
The vertical axis shows the boiler temperature and the horizontal axis shows the outdoor temperature.
°C
10
20
30
40
50
60
-30
-20
-10
0
10
20
0
50
30
40
°C
20
Delivery setting