Värmebaronen EK 15E

Troubleshooting - Warning, limitation and alarms

Limit

Connection delay

Delayed output connection after restart after power failure.

 

Upon restart after power loss, up to 6 kW is connected immediately if necessary.

 

In service mode, the delay can be accelerated, see "Service level" row 2.

 

The delay can be permanently removed, see "Advanced Service level", row 14.

The load guard limits

Green indicator flashes. The load guard limits.

 

See "Service level" rows 3 and 4.

External restriction / 

blocking

Green indicator flashes. External limit.

 

Blocking or restriction via external 0-10V signal, see "User level" row 3.

Manual operation

Manual connection of output stages and circulation pump, see "Advanced Service level" 
rows 18-20.

ECO mode

Green indicator flashes. ECO function is active, see "User level" row 12.

Warning - yellow indicator flashing

The display shows current warnings if no stop alarms occur. The information remains until OK is pressed and the cause 
has been resolved.

High temperature 
around power 

circuit board

Temperature > 45°C.

 

Yellow indicator goes off at temperature below 42°C, the warning is acknowledged 
with OK.

 

All connected output steps out at temperatures > 55°C, output can be stepped back 
in at temperatures < 45°C, see "Advanced service level" row 24.

High boiler temperature

Over Temperature.

 

Yellow indicator goes off when temperature has fallen below the limit and the warning 

is acknowledged with OK. All connected output steps out and steps in again only when 
the temperature has dropped below the limit. Selectable in "Advanced Service level" 
rows 16 and 7.

Low boiler temperature

Boiler temperature lower than 7°C.

 

The electric flow heater's temperature must be no lower than 7°C during operation, 
regardless of the selected setpoint.

 

If external blocking / external control is active, the electric flow heater is 

NOT

 allowed 

to step in output.

 

If the load guard restricts, the electric flow heater is 

NOT

 allowed to step in output.

Outdoor sensor

Incorrect value, interruption, disconnected sensor or short-circuit.

 

Control assumes 0°C outdoor temperature.

Room device

Incorrect value, interruption / short circuit of the sensor and / or disconnected room unit.

 

The unit is disconnected from the control until the alarm is acknowledged and the room 
unit is repaired.

Room unit, adjustment

Incorrect value, interruption / short circuit or disconnection of the room unit. The unit 

is disconnected from the control until the alarm is acknowledged and the room unit 

is repaired.

Alarm - red indicator flashes: the electric flow heater is blocked

Display window shows current alarms. The information remains until the cause is corrected and OK is pressed

Boiler temperature 
sensor

Incorrect value or interruption / short circuit on sensor.

Temperature sensor 

on circuit board

Incorrect value or interruption / short circuit on sensor.

Low boiler temperature

Boiler blocked due to a boiler temperature lower than 3°C.

Overheating protection 
triggered

All output disconnected, the circulation pump is still in operation.

Low supply voltage

Low supply voltage to electronic components, all output disconnected, the circulation 
pump is switched off.

Содержание EK 15 E

Страница 1: ...Installation and maintenance EK 15 E Electric flow heater 7 stage 14 7 kW 1212_EK15E_191017_en pwr 1 14 1 15 dsp 1 05 p typ 4...

Страница 2: ...sator setpoints UTK Alternative temperature Alternative temperature with room unit Optional Room Unit Over temperature protection Overheating protection Action in the event of a risk of freezing Frost...

Страница 3: ...onthat is important for optimum operation Tells you what you should or should not do to avoid personal injury Tells you what you should or should not do to prevent a component the electric flow heater...

Страница 4: ...the value is changed the indicator flashes The new value is only applied after confirming by pressing The old value is removed if the row is left with or User level Reading and modification of the mos...

Страница 5: ...rent alarm codes according to a rolling schedule Once the cause of the alarm is resolved and is acknowledged with OK the red indicator stops flashing The display will return to its normal display Ackn...

Страница 6: ...rve parallel displacement 5 30 adjustment 20 UTK function switched off see Advanced Service Level row 15 Curve higher value provides warmer temperatures for cold outdoor temperatures 20 60 adjustment...

Страница 7: ...time to stabilize UTK function switched off see Advanced Service Level row 15 Alternative temperature 15 15 C Adjustment See Outdoor temperature sensor and alternative heating in Electrical installat...

Страница 8: ...ut 2 1 4 2 6 3 8 4 10 5 12 6 14 7 kW Current 3 6 05 9 1 12 1 15 1 18 1 21 2 A 7 UTK function switched off see Advanced Service Level row 15 UTK min Limitation of the supply line temperature Adjustment...

Страница 9: ...16 above At Absolute temperature the selected temperature should not exceed 10 C 10 Manual activation of rows 19 and 20 Adjustment 0 Off 1 Limited to 15 minutes 0 Manual activation test run of output...

Страница 10: ...see Advanced Service Level line 14 For testing and service the connection delay and output connect disconnect can be temporarily sped up see Service level rows 1 and 2 The electric flow heater should...

Страница 11: ...few more times The pressure in a heating system varies with the temperature Do not add water unnecessarily Draining If the heating system needs to be drained of water the electric flow heater must fi...

Страница 12: ...ontain corrosion limiting additives Suitable water line quality Alkalinity 60 mg l to avoid corrosion Carbonic acid content 25 mg l increase the risk of corrosion Sulphate contents 100 mg l may accele...

Страница 13: ...and must be laid so that water pockets cannot form The opening pressure of the safety valve is determined by the component in the system that tolerates the lowest pressure System principles The figure...

Страница 14: ...conductor is connected in terminal 4 10 Electrical installation Electrical installation shall be carried out in accordance with the applicable regulations by an authorized electrical installer or by...

Страница 15: ...er 14 Overheating protection 15 Contactor power group three 16 Heating element output group three 8 4 kW 17 Heating element for output group two 4 2 kW 18 Heating element for output group one 2 1 kW W...

Страница 16: ...ain only when the temperature has dropped below the limit Selectable in Advanced Service level rows 16 and 7 Low boiler temperature Boiler temperature lower than 7 C The electric flow heater s tempera...

Страница 17: ...ard during resistance measurement When the boiler is energized voltage is measured in the sensor s connection points at the PCB Boiler temperature C k V C k V C k V 5 141 9 4 7 40 30 3 7 75 8 2 2 3 10...

Страница 18: ...tage size 2 1 kW Current stage 3 A Ingress protection rating IP x1 Flow requirements recommended t 10 C min max t 25 5 C 0 35 0 2 0 7 litres sec litres sec Pressure drop Volume 3 6 litres Design press...

Страница 19: ...panel 1 700414 Overlay 1 6 210206 Temperature sensor 1 11 440090 Capacitor 1 12 130010 Switch 1 120009 Knob for switch 1 700223 Shaft for switch 1 13 180023 Miniature circuit breaker 1 14 120025 Over...

Страница 20: ...V rmebaronen AB Arkelstorpsv gen 88 SE 291 94 Kristianstad Tel 46 44 22 63 20 www varmebaronen se www varmebaronen com info varmebaronen se...

Отзывы: