Operation and maintenance

Before starting, check that the installation is in a 

fully satisfactory condition.

 

Ask the installation engineer to demonstrate 

the control and functions so that you know how 

the system works and must be maintained.

Check:

•  

Boiler and heating system are filled with water, 

vented and that the pressure is correct.

• 

That all necessary valves are open.

• 

That any safety valves are working.

•  

That any external safety equipment is working 

as intended.

•  

That the circulation pump is working and 

the flow direction is correct.

Start

Energised electric flow heater, the display illuminates 
along with a green indicator.

A number of parameters are shown below that should 

be considered when starting:

For installation / configuration, see "Menu - 

Management"!

•  Stage restriction; "Service level" row 5.
•  Load guard; "Service level" row 3.
•  Circulation pump; "Advanced Service level" 

rows 20 and 23.

•  External control / Output control; "Advanced Service level" 

row 13.

•  ECO-mode; "User level" row 12.

Depending on whether the electric flow heater will be 

controlled by a fixed or outdoor-compensated, UTK, setpoint. 
For the UTK function, the electric flow heater must be 
supplemented with an outdoor temperature sensor, optional.
• Desired boiler temperature; "User level" row 1.
•  UTK; "Advanced service level" rows 5, 6, 7, 8 and 9 

and "Service level" rows 6, 7 and 8.

•  Room unit; "User level" rows 10 and 11 and 

"Service level" row 8.

 

The room unit is an option and requires that the 
UTK function is activated.

Depending on the selected connection delay upon restart 

after power failure, a connection delay can be applied for 
output connection over 6 kW, see "Advanced Service Level" 
line 14.
For testing and service, the connection delay and 
output connect / disconnect can be temporarily sped up, 
see "Service level" rows 1 and 2.

The electric flow heater should now step in the number 
of output stages needed until the temperature conforms 
to the set value.

Connection delay

According to the recommendations, a maximum of 6 kW 
of the output should be connected immediately after 
a voltage loss.

 

See "Advanced Service level" row 14.

Circulation pump

Operating modes for circulation pump, see "Advanced 
Service level" rows 20 and 23.

Load guard

The load guard protects the main fuses against overload 
by reducing the electric flow heater's output. When the 
overload ceases, the output is reconnected stage by stage.

 

See "Service level" row 3.

Stage restriction

The flow heater can be stage restricted in 1-7 stages. 
The number of stages selected corresponds to the installed 
output. See "Service level" row 5.

Output limitation / Output control, 0-10V

 Output restriction; the electric flow heater's temperature 
control is superior; the setpoint must be set slightly higher 
than the required temperature.
Output control, only the overtemperature limit restricts. Used 
together with another unit with its own temperature control.
See "Advanced Service level" row 13.

Desired boiler temperature

Desired boiler temperature, setpoint, see "User level" row 1.

Outdoor temperature compensator setpoints, UTK

The Elomax electric flow heater must be supplemented with 
an outdoor temperature sensor-option. This function must 
be activated in the menu system.

 

See "Advanced level" rows 5, 6, 7, 8 and 9 and "Service 
level" rows 6, 7 and 8.

Alternative temperature

This function requires that the UTK function is activated and 
an external contact. Can be used for night-time reduction, 
holiday mode or similar, see "User level" rows 6 and 9.

Содержание EK 15 E

Страница 1: ...Installation and maintenance EK 15 E Electric flow heater 7 stage 14 7 kW 1212_EK15E_191017_en pwr 1 14 1 15 dsp 1 05 p typ 4...

Страница 2: ...sator setpoints UTK Alternative temperature Alternative temperature with room unit Optional Room Unit Over temperature protection Overheating protection Action in the event of a risk of freezing Frost...

Страница 3: ...onthat is important for optimum operation Tells you what you should or should not do to avoid personal injury Tells you what you should or should not do to prevent a component the electric flow heater...

Страница 4: ...the value is changed the indicator flashes The new value is only applied after confirming by pressing The old value is removed if the row is left with or User level Reading and modification of the mos...

Страница 5: ...rent alarm codes according to a rolling schedule Once the cause of the alarm is resolved and is acknowledged with OK the red indicator stops flashing The display will return to its normal display Ackn...

Страница 6: ...rve parallel displacement 5 30 adjustment 20 UTK function switched off see Advanced Service Level row 15 Curve higher value provides warmer temperatures for cold outdoor temperatures 20 60 adjustment...

Страница 7: ...time to stabilize UTK function switched off see Advanced Service Level row 15 Alternative temperature 15 15 C Adjustment See Outdoor temperature sensor and alternative heating in Electrical installat...

Страница 8: ...ut 2 1 4 2 6 3 8 4 10 5 12 6 14 7 kW Current 3 6 05 9 1 12 1 15 1 18 1 21 2 A 7 UTK function switched off see Advanced Service Level row 15 UTK min Limitation of the supply line temperature Adjustment...

Страница 9: ...16 above At Absolute temperature the selected temperature should not exceed 10 C 10 Manual activation of rows 19 and 20 Adjustment 0 Off 1 Limited to 15 minutes 0 Manual activation test run of output...

Страница 10: ...see Advanced Service Level line 14 For testing and service the connection delay and output connect disconnect can be temporarily sped up see Service level rows 1 and 2 The electric flow heater should...

Страница 11: ...few more times The pressure in a heating system varies with the temperature Do not add water unnecessarily Draining If the heating system needs to be drained of water the electric flow heater must fi...

Страница 12: ...ontain corrosion limiting additives Suitable water line quality Alkalinity 60 mg l to avoid corrosion Carbonic acid content 25 mg l increase the risk of corrosion Sulphate contents 100 mg l may accele...

Страница 13: ...and must be laid so that water pockets cannot form The opening pressure of the safety valve is determined by the component in the system that tolerates the lowest pressure System principles The figure...

Страница 14: ...conductor is connected in terminal 4 10 Electrical installation Electrical installation shall be carried out in accordance with the applicable regulations by an authorized electrical installer or by...

Страница 15: ...er 14 Overheating protection 15 Contactor power group three 16 Heating element output group three 8 4 kW 17 Heating element for output group two 4 2 kW 18 Heating element for output group one 2 1 kW W...

Страница 16: ...ain only when the temperature has dropped below the limit Selectable in Advanced Service level rows 16 and 7 Low boiler temperature Boiler temperature lower than 7 C The electric flow heater s tempera...

Страница 17: ...ard during resistance measurement When the boiler is energized voltage is measured in the sensor s connection points at the PCB Boiler temperature C k V C k V C k V 5 141 9 4 7 40 30 3 7 75 8 2 2 3 10...

Страница 18: ...tage size 2 1 kW Current stage 3 A Ingress protection rating IP x1 Flow requirements recommended t 10 C min max t 25 5 C 0 35 0 2 0 7 litres sec litres sec Pressure drop Volume 3 6 litres Design press...

Страница 19: ...panel 1 700414 Overlay 1 6 210206 Temperature sensor 1 11 440090 Capacitor 1 12 130010 Switch 1 120009 Knob for switch 1 700223 Shaft for switch 1 13 180023 Miniature circuit breaker 1 14 120025 Over...

Страница 20: ...V rmebaronen AB Arkelstorpsv gen 88 SE 291 94 Kristianstad Tel 46 44 22 63 20 www varmebaronen se www varmebaronen com info varmebaronen se...

Отзывы: