Feature 09 – Floor Temp Limit: 

This function is available 

when mode 08 is set to 03 or 04. You can set a floor limiting 

temperature between 20-45°C (28°C is the default). 

 

Feature 10 – Optimum Start

: Optimum start will delay the 

start up of the heating system to the latest possible moment to 
avoid unnecessary heating, so that the dwelling is comfortably 
warm by the programmed time. The thermostat uses the rate of 
change (see below) setting to calculate how long the building 
needs to take to raise the building 1°C (With a rate of change 
of 20, the thermostat has calculated the building needs 20 

minutes to raise the building 1°C). On this thermostat, optimum 
start works on the Wake and Return comfort levels. 

 

Feature 11 - Rate of Change: 

For information only. 

 

Feature 12 - Weekday/Weekend or 7 Day Programming

The thermostat offers two programming methods. Weekday/ 
Weekend allows you to program 4 comfort levels for the 
weekday and 4 different comfort levels for the weekend. In 7 
day program mode, each day has 4 comfort levels that can be 
programmed independently. 

Содержание FH-01

Страница 1: ...1 Operating Instructions Model FH 01 230V A C 16Amp Digital Thermostat Programmer For Electric Underfloor Heating Version 2 April 2010...

Страница 2: ...6 Setting the Clock 6 Setting the Comfort Levels 7 Keypad Lock Facility 8 Temperature Hold 9 Setting the Temperature 9 Holiday Feature 10 Frost Protection Power On Off 11 Factory Reset 11 Operating Mo...

Страница 3: ...he thermostat should be mounted in a 35mm min deep back box Step 1 Carefully separate the front half of the thermostat from the back plate by placing a small flat head terminal driver into the slots o...

Страница 4: ...4 LCD Display Controls 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18...

Страница 5: ...am Cycle Indicator Displayed during programming only to show which period is being altered 8 Holiday Indicator Displayed when the programmer is in holiday mode 9 Clock Button 10 Power Button 11 H Butt...

Страница 6: ...e thermostat is set to use both sensors the room temperature will normally be shown To view the floor temperature press and hold the A key until the Floor Temperature is shown Setting The Clock To set...

Страница 7: ...these can be changed easily The default times are 08 00 21 C Wake 09 30 16 C Leave 16 30 22 C Return 23 00 17 C Sleep If you only want to use 2 levels you should program the unused levels to To begin...

Страница 8: ...d periods Note For weekday weekend Programming the 4 comfort levels are the same for all weekdays For 7 day programming each day can have 4 different comfort levels Locking The Thermostat The thermost...

Страница 9: ...H Using the Up Down arrow keys enter the required hold temperature Press A to accept You will see the Hold indication is displayed which will countdown the hold duration To cancel reduce the Hold time...

Страница 10: ...r holiday the thermostat will revert back to the programmed setting ensuring that your home is warm on your arrival Press H three times Until you see the suitcase Using the Up Down arrow keys enter th...

Страница 11: ...ost protect mode press the Power button Thermostat Off To turn the thermostat off completely press and hold the Power button The display and heating output will be turned off To turn the thermostat ba...

Страница 12: ...fault Operating Mode The thermostat has 4 main operating modes Select the mode that best suits your needs Note Mode 00 or 02 MUST not be used to control underfloor heating Mode 01 or 03 default should...

Страница 13: ...at with a set temperature of 20 C the thermostat will switch the heating on at 19 C and off at 20 C With a 2 C differential the heating will switch on at 18 C and off at 20 C Feature 03 Frost Protect...

Страница 14: ...arrow keys This limit is also applicable when the thermostat is locked and so allows you to give others limited control over the heating system Feature 08 Sensor Selection On this thermostat you can...

Страница 15: ...setting to calculate how long the building needs to take to raise the building 1 C With a rate of change of 20 the thermostat has calculated the building needs 20 minutes to raise the building 1 C On...

Страница 16: ...small number is the feature number the large number is the setting value 3 Use the clock button to cycle through the features 4 Use the Up Down keys to change the setting 5 Press A to accept and store...

Страница 17: ...00 MUST not 01 Remote Air Sensor be used for 02 Floor Sensor Only Underfloor heating 03 Floor Sensor and Built in Air Sensor 04 Floor Sensor and Remote Air Sensor 09 Floor Temp Limit 20 45 C 28 C Defa...

Страница 18: ...g Element Neutral 5 230V Supply Neutral 6 Heating Element Live 7 230V Supply Live nb generally underfloor heating elements floor sensors are not polarity conscious as such can be connected to the live...

Страница 19: ...19 Notes E1 Floor Sensor is not connected or is faulty E2 Remote Air Sensor is not connected or is faulty E3 Built In Air Sensor is not connected or is faulty Error Codes...

Страница 20: ...20...

Отзывы: