Multi-Element Temperature Transmitter
15
Installation and Operations Manual
1
Only displayed if in Display Mode
2
Only displayed if in Alter Mode
3
Only displayed if TRUE
Diagnostics Menu
Description
Bad EEPROM
3
EEPROM holding the configuration data could not be written to.
Bad EE Cksum
3
EEPROM configuration data's checksum is bad. Review all
configuration data and perform an Exit and Save.
Bad RAM
3
RAM chip is bad.
Bad EPROM
3
Program memory is bad.
HART Polls
3
Number of HART polls received since power-up/new configuration
write. (0-65535 and resets to 0 after full value)
HART Errors
3
Number of HART communication errors encountered since power-
up/new configuration write. (0-65535 and resets to 0 after full
value)
Bottom Temperature
Temperature at bottom probe
Temperature 1
Temperature at probe number 1
Temperature 2
Temperature at probe number 2
Temperature 3
Temperature at probe number 3
Temperature 4
Temperature at probe number 4
Temperature 5
Temperature at probe number 5
Temperature 6
Temperature at probe number 6
Temperature 7
Temperature at probe number 7
Temperature 8
Temperature at probe number 8
Temperature 9
Temperature at probe number 9
Temperature 10
Temperature at probe number 10
Top Temperature
Temperature at top probe.