MODBUSAppendix A — MODBUS Implementation
Varec, Inc.
153
If a variable goes out-of-bounds (outside the minimum or maximum scale points), a value
equal to the maximum MODBUS i 1 is returned. Writing to dynamically calculated
parameters has no effect on those parameters.
Coded data
Coded data represents a table look-up value. Data written to these registers must be a valid
table entry. Invalid data may cause a Configuration Error to occur. The following example
shows coded data at data address 20 (0014 Hex) representing level units. The value 44
(002C Hex) returned from the 2920 FTT corresponds to level units = Feet.
• Hexadecimal
representation
0001
• Level unit table representation: FT
Packed Bit Data
Packed bits represent 16 individual status bits packed into one register. The status bits have
been packed this way for systems that prefer handling only register information. These bits
may also be read or written individually using a bit command. The bits within the packed
registers are grouped by data or function type. The following communication example of
packed bits shows alarm status information at data address 5 (0005 Hex) returned by the 2920
FTT.
Note
Bit #0 is ON indicating a critical low level Alarm
Host Request
Address
Function
Code
Start Reg
H
Start Reg
L
# of Reg
H
# of Reg
Error
Check
01
03
00
14
00
01
C4 0E
2920 FTT Response
Address
Function
Code
Byte Count
Data
MSB
Data
LSB
Error
Check
01
03
02
00
2C
B9 99
Host Request
Address
Function
Code
Start Reg
H
Start Reg
L
# of Reg
H
# of Reg
L
Error
Check
01
03
00
05
00
01
94 0B
2920 FTT Response
Address
Function
code
Byte Count
Data
MSB
Data
LSB
Error
Check
01
03
02
00
01
79 84
Содержание 2920
Страница 2: ......
Страница 16: ...2920 Float Tape Transmitter 1 Introduction 6 Installation and Operations Manual...
Страница 114: ...2920 Float Tape Transmitter 6 Bi Phase Mark 104 Installation and Operations Manual...
Страница 120: ...2920 Float Tape Transmitter 7 MODBUS 110 Installation and Operations Manual...
Страница 126: ...2920 Float Tape Transmitter 9 L J TankWay 116 Installation and Operations Manual...
Страница 138: ...2920 Float Tape Transmitter 11 Configuration Calibration Level Limits and Outputs 128 Installation and Operations Manual...
Страница 148: ...2920 Float Tape Transmitter 12 Maintenance and Troubleshooting 138 Installation and Operations Manual...
Страница 158: ...2920 Float Tape Transmitter 14 Ordering Information 148 Installation and Operations Manual...
Страница 178: ...2920 Float Tape Transmitter MODBUSAppendix A MODBUS Implementation 168 Installation and Operations Manual...
Страница 193: ......