2920 Float & Tape Transmitter
12 Maintenance and Troubleshooting
134
Installation and Operations Manual
5. Using the icons or the Point menu, select a point. The dialog box for that point appears.
6. View or edit the information as needed. Refer to "Display and Configuration Interface" for
information about each database point.
7. Repeat steps 5 and 6 as needed for other points.
8. Close ViewRTU.
9. Disconnect the laptop computer cable from the RS-232 connector.
10. Replace the 2920 FTT cover.
Returning the 2920 FTT to Factory Default Settings
Note
This procedure resets all level and temperature alarm setpoints.
The 2920 FTT can be reset to factory default setting in using either of the procedures below:
This procedure initializes all 2920 FTT configuration parameters to factory default settings,
using the display interface.
Содержание 2920
Страница 2: ......
Страница 16: ...2920 Float Tape Transmitter 1 Introduction 6 Installation and Operations Manual...
Страница 114: ...2920 Float Tape Transmitter 6 Bi Phase Mark 104 Installation and Operations Manual...
Страница 120: ...2920 Float Tape Transmitter 7 MODBUS 110 Installation and Operations Manual...
Страница 126: ...2920 Float Tape Transmitter 9 L J TankWay 116 Installation and Operations Manual...
Страница 138: ...2920 Float Tape Transmitter 11 Configuration Calibration Level Limits and Outputs 128 Installation and Operations Manual...
Страница 148: ...2920 Float Tape Transmitter 12 Maintenance and Troubleshooting 138 Installation and Operations Manual...
Страница 158: ...2920 Float Tape Transmitter 14 Ordering Information 148 Installation and Operations Manual...
Страница 178: ...2920 Float Tape Transmitter MODBUSAppendix A MODBUS Implementation 168 Installation and Operations Manual...
Страница 193: ......