LifeSine LSC12-2000 - Owner’s Manual
1 -
True Sinewave
Inverter/Charger
Model LSC12-2000
Страница 1: ...VANNER Incorporated Owner s Manual LifeSine LSC12 2000 Owner s Manual 1 True Sinewave Inverter Charger Model LSC12 2000...
Страница 2: ...and installation precautions 1 1 4 Warning regarding the use of batteries 2 2 FUNCTION CHARACTERISTICS INTRODUCTION 3 2 1 System overview 3 2 2 Electrical specification 4 2 3 Mechanical drawings 6 3 I...
Страница 3: ...to these batteries in permanent systems For the conversion of a DC voltage from a battery to and AC voltage Do not expose the unit to rain snow spray or dust To reduce the risk of fire hazard do not c...
Страница 4: ...between the batteries and the unit cannot prevent damage caused by reversed polarity and the warranty will be void Do not work on unit or system if it is still connected to a power source Only allow...
Страница 5: ...signal processor technology offering the following features Bi directional All in One Design Certified by UL UL458 Vehicle Supplement SA Compact Size Highly Integration Installation hassle free Batte...
Страница 6: ...3 Surge Power Load 101 115 1 Min 4000 VA 2 Sec Frequency 50 60 Hz 0 3 Hz User selectable Output Voltage 100 110 115 120VAC 3 Max Efficiency Full Load 89 Output Waveform Pure Sine Wave THD 5 12 5V 25V...
Страница 7: ...Transfer Time 0 sec Operating Temperature Range Full Load 20 40 Power de rating 60 W 41 60 Storage 30 70 Operating Humidity Range Max 93 Non condensing Cooling Temperature Load Controlled Cooling Fan...
Страница 8: ...6 De rating Curve Fig 2 LSC12 2000 De rating Curve 2 3 Mechanical drawings Unit mm inch Fig 3 LSC12 2000 Mechanical drawings...
Страница 9: ...fication label whether the battery voltage is the same as the DC input voltage of the unit e g 12V battery set for a 12V input voltage Also check that the AC output voltage and output power of the uni...
Страница 10: ...n utility power is available on the AC input and the unit is in charger mode this connection must be disabled again In some applications automatic connection between the neutral conductor N and earth...
Страница 11: ...Table 6 Output frequency function definition 3 2 1 3 AC Input Current Limit Select S4 S5 S6 Default 15A AC Input Current 100 120V S4 S5 S6 3A OFF OFF OFF 6A ON OFF OFF 9A OFF ON OFF 12A ON ON OFF 15A...
Страница 12: ...ut load 20W 10seconds Saving function S12 OFF OFF ON ON Table 11 Saving function switch On Off function definition 3 2 2 Status LED indicator Icon Description Icon Description Battery Input voltage in...
Страница 13: ...Over Current Protect Red Off Inverter mode Solid ON Battery Under voltage 12V 11 0V 24V 22 0V Battery Over voltage 12V 15 5V 24V 31 0V Over load 115 Over Load Short Circuit Protection Slow Blink Batte...
Страница 14: ...uation Batteries are capable of providing very large currents in case of short circuit In case there is a short circuit in the cable run between the batteries and the input terminals of the unit it wi...
Страница 15: ...trol terminal Item Description Item Description 1 Dry contact Normal Open 4 Enable ENB 2 Common 5 Enable ENB 3 Dry contact Normal Closed 6 Ground RS 232 Remote control port Use 20 24 AWG wire to conne...
Страница 16: ...14 G Fan speed control The fan turned on by Load or Temp C as below chart Note the fan full speed 100 turned when the status of over temperature the circuit short and the over load occur...
Страница 17: ...ty This causes the battery charger to look like a resistor to the line forces the charge current wave shape to mirror the voltage wave shape The PI feature allows the charger voltage and current to ch...
Страница 18: ...the end of the absorb charging time While final charging the charge voltage is reduced to the final charge voltage determined by the Battery Type selection In this stage the batteries are kept fully...
Страница 19: ...f the LSC12 2000 inverter will trigger OLP over load protection when the output power is over loaded It can protect the input AC power device such as the utility or generator power system CAUTION For...
Страница 20: ...2 Check the setup value of AC input current limit Dip Switch S4 S5 S6 3 Re turn on the unit manually Solid N A Phase or Frequency Failure 1 Make sure AC input frequency matches the Unit output frequen...