Engineer programming via the keypad
16
Communication
141
Vanderbilt
Installation & Configuration Manual
A6V10276959
01.05.2016
2. Press SELECT.
The IP ADDRESS option displays, XXX.XXX.XXX.XXX For single digits,
leading zero(s) are required. Ie., 001
3. Press SELECT and enter the preferred IP address.
When the ENTER key is operated, the system beeps twice and states
UPDATED if the IP address is valid. If the IP address is allocated manually,
then this must be unique on the LAN or VLAN, connected to panel. A value
is not entered if the DCHP option is used.
4. Scroll to IP NETMASK.
5. Press SELECT and enter the IP NETMASK format XXX.XXX.XXX.XXX. (For
single digits, leading zero(s) are required. Ie., 001) When the ENTER key is
operated, the system beeps twice and states UPDATED if the IP NETMASK is
valid.
6. Scroll to GATEWAY. Note the gateway needs to be programmed for access
outside the network (for use with the Portal).
7. Press SELECT and enter the GATEWAY format XXX.XXX.XXX.XXX. (For
single digits, leading zero(s) are required. Ie., 001) When the ENTER key is
operated, the system beeps twice and states UPDATED if the GATEWAY is
valid.
8. Scroll to DHCP. The DHCP is enabled if the LAN has a DHCP server to
allocate the IP address. The IP address is to be enabled manually. Note the
gateway needs to be programmed if the panel needs access outside the
network (for Portal service).
9. Press SELECT and enter the GATEWAY format XXX.XXX.XXX.XXX. (For
single digits, leading zero(s) are required. Ie., 001)
When the ENTER key is operated, the system beeps twice and states
UPDATED if the GATEWAY is valid.
The DHCP option is displayed.
10. Toggle between DHCP ENABLED and DISABLED for preferred option.
11. Press SELECT.
16.11.3
Modems
The SPC system supports SPC intelli-modems for communications with analogue
lines and mobile network interfacing for enhanced communications and
connectivity. The SPC system must be configured accordingly.
16.11.3.1
Monitoring the transmission network interface
The SPC Alarm System sends a poll to SPC Com XT, which responds with a poll
acknowledge (ACK). On receipt of a valid poll ACK the SPC Alarm System updates
its status to OK and resets its polling interval timer (depending on the ATP
category).
If the SPC Alarm System does not receive a polling ACK within the timeout
(depends on ATP category), the SPC Alarm System updates its status to DOWN.
SPC supports the following transmission interfaces:
Ethernet
GSM with GPRS enabled
PSTN modem.
Содержание SPCK620
Страница 1: ...A6V10276959 Vanderbilt 01 05 2016 SPC42xx 43xx 52xx 53xx 63xx Installation Configuration Manual 3 6 ...
Страница 364: ...23 Appendix ATP Category Timings 364 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 365: ...Appendix 23 ATP Category Timings 365 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 366: ...23 Appendix ATP Category Timings 366 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...
Страница 367: ...Appendix 23 ATP Category Timings 367 Vanderbilt Installation Configuration Manual A6V10276959 01 05 2016 ...