The configuration requirements for a Blocking Lock are as follows:
l
Outputs:
– Ready to set
– Setting Ack
– Fullset Done
– Blockschloss 1/2
l
Inputs
– Keyarm
22.2 Authorized Setting of the Blocking Lock
The ‘Authorised Setting‘ functionality extends the setting and unsetting procedure for a Blocking Lock with
a second security level. Before the system can be set or unset, a code must be entered on an external
setting device such as a card or pin reader with a separate controller. This controller can be connected to
any kind of intrusion system using inputs and outputs.
Operation is as follows:
1. The panel signals to the external setting device when it is possible to set using a Ready To Set
output.
2. When the code is entered, the Setting Authorisation input is activated and Blockschloss 1/2 is
activated.
3. The blocking lock opens a control panel input (Keyarm) which initiates the setting procedure of the
panel.
4. The external setting device waits up to 8 seconds for Fullset Done output signal to be activated from
the control panel.
5. If this signal is not received, the setting fails and the external setting device unsets the system
again.
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual
Blocking Lock Operation
© Vanderbilt 2018
358
A6V10276959-d
11.2018