Note:
Batteries must have sufficient charge to supply the load.
6. Reconnect mains power.
Green LED should be on.
7. Remove Load fuse and check that the red Fault LED is on (dependent on model).
2.2.5 Tamper
A tamper condition is reported in software.
1. Check that the tamper switch is:
l
Closed when the enclosure is mounted on the wall, lid is closed, and the lid screw is fitted.
l
Open when the lid is open.
2. Close cover and secure using fastening screw(s) provided.
2.2.6 Ferrite bead installation for the ACT365-VCU2A
While installing the ACT365-VCU2A, Vanderbilt recommend that you place the provided ferrite cores
(noise-suppression devices) around the Ethernet and power cables to attain a desired level of
electromagnetic compatibility (EMC).
Power cable ferrite core (
A
)
Inner diameter 19.05mm, outer diameter
31.12mm, length 15.93mm
Ethernet ferrite core (
B
)
Inner diameter 12.83mm, outer diameter
25.91mm, length 28.58mm
To install the ferrite cores:
1. Wind the power cable around ferrite core
A
with two turns.
2. Wind the Ethernet cable around ferrite core
B
with two turns.
ACT365-VCU / ACT365-VCU2A / ACT365-VCUPoE – Installation and Operating Instructions
Installation
© Vanderbilt 2019
12
A-100528-b
20.05.2019