6.2 Communication protocols
6 Communication
Technical description
144
VAMP 24h support phone +358 (0)20 753 3264
VM265.EN011
6.2.4.
SPA-bus
The manager has full support for the SPA-bus protocol
including reading and writing the setting values. Also reading
of multiple consecutive status data bits, measurement values or
setting values with one message is supported.
Several simultaneous instances of this protocol, using different
physical ports, are possible, but the events can be read by one
single instance only.
There is a separate document “Spabus parameters.pdf” of SPA-
bus data items available.
Parameters
Parameter Value
Unit Description
Note
Addr
1
899
SPA-bus address. Must be
unique in the system.
Set
bit/s
1200
2400
4800
9600 (default)
19200
bps
Communication speed
Set
Emode
Channel
(Limit60)
(NoLimit)
Event numbering style.
Use this for new
installations.
(The other modes are for
compatibility with old
systems.)
(Set)
Set = An editable parameter (password needed)