3.6 Running hour counter
3 Supporting functions
Technical description
112
VAMP 24h support phone +358 (0)20 753 3264
VM265.EN011
*) Astronomically a range –11 ... +12 h would be enough, but for political
and geographical reasons a larger range is needed.
**) If external synchoronization is used this parameter will be set
automatically.
***) Set the DI delay to its minimum and the polarity such that the leading
edge is the synchronizing edge.
3.6.
Running hour counter
This function calculates the total active time of the selected
digital input, virtual I/O or output matrix output signal. The
resolution is ten seconds.
Running hour counter parameters
Parameter Value
Unit Description
Note
Runh
0 ... 876000
h
Total active time, hours
Note: The label text "Runh" can
be edited with VAMPSET.
(Set)
0 ... 3599
s
Total active time, seconds
(Set)
Starts
0 ... 65535
Activation counter
(Set)
Status
Stop
Run
Current status of the selected
digital signal
DI
-
DI1 ...DI6,
VI1...VI4,
LedAl,
LedTr,
LedA,
LedB,
LedC,
LedDR
VO1...VO6
Select the supervised signal
None
Physical inputs
Virtual inputs
Output matrix out signal Al
Output matrix out signal Tr
Output matrix out signal LA
Output matrix out signal LB
Output matrix out signal LC
Output matrix out signal DR
Virtual outputs
Set
Started at
Date and time of the last
activation
Stopped at
Date and time of the last
inactivation
Set = An editable parameter (password needed).
(Set) = An informative value which can be edited as well.
Содержание 265
Страница 2: ...VM265 EN011...
Страница 214: ...11 Construction Technical description 214 VAMP 24h support phone 358 0 20 753 3264 VM265 EN011 11 Construction...
Страница 219: ...VM265 EN011...