Clearances—Combustible Mantel

L2 1700K

Bottom of Unit

0 2” 4” 6” 8” 10”12”

Face of 1/2” thick

non-combustible

cement board

Do not put

furniture or objects

within 36” [914 mm]

of front of appliance 

Mantel Projection

(from Face of Cement Board)

Mantel

Height

(from

Bottom

of Unit)

Fireplace 

Opening

Ceiling

36” Min. to Ceiling

44”
42”
40”
38”

23-7/8”

9-3/8”

4” minimum to 

combustible or 

non-combustible hearth

Left Side View

NOTE

Use for the optional HeatShift 

System affects mantel and hearth 

clearances. See HeatShift section in 

Appendix D of Installation Manual.

WARNING

HeatShift System MUST be installed 

on this appliance when using 

1730CIK—Clean Installation Kit!