14
TECHNIC
AL SPECIFIC
ATIONS
SUPPLY/EXTRACT AIR VOLUMES
VALLOX 245 MV VKL
FAN INPUT POWER
40
144
50 %
30 %
70 %
100 %
50
100
150
200
250
300
350
0
60
80
100 120
160
140
180 200 220
260 280
240
216 288 360 432 504
576 648 720 792 864 936 1008
300
1080
dm³/s
(l/s)
m³/h
60
80
100
120
160
140
180 200 220
260 280
240
216
288 360 432 504
576 648 720 792 864
936 1008
300
1080
50
100
150
200
250
300
350
400
70 %
100 %
50 %
30 %
40
144
m³/h
(l/s)
dm³/s
Volume flow rate
(dm
3
/s)
Pressure loss in ducts. Total pressure (Pa)
Volume flow rate
Power (W)
Input power (total) (W)
Air flow (max) (dm3/s)
SFP =
SFP rate (Specific Fan Power)
recommended value <1.8 (kW m
3
/s)
extract air
supply air
Sound power level in the supply air duct (one duct)
by octave band L
w
, dB
Sound power level in the extract air duct (one duct)
by octave band L
w
, dB
Adjustment position
Adjustment position
Adjustment position (%)
54
100
50
100
Air flow dm³/s
181
221
204
278
Air flow m³/h
652
796
734
1001
Medium
frequency
of the
octave
band Hz
63
72
76
60
66
125
67
71
57
62
250
65
69
61
66
500
59
66
46
52
1000
57
62
45
51
2000
57
62
41
47
4000
46
52
30
38
8000
40
47
25
28
L
W
,dB
L
WA
, dB(A)
74
79
64
70
63
69
53
59
Sound pressure level coming through the envelope of the unit in the room in which it is installed (10m² sound absorption)
Adjustment position / Air flows (supply/extract)
Adjustment position (%)
54/44
100/100
Air flow dm³/s
181/190
221/282
Air flow m³/h
652/684
796/1015
L
pA
, dB (A)
42
48
SOUND VALUES
TECHNICAL SPECIFICATIONS
Product title
Vallox 245 MV VKL R
Vallox 245 MV VKL L
Product number
3513150
3513250
Air volumes
Supply air
Extract air
219 dm
3
/s, 100 Pa
267 dm
3
/s, 100 Pa
Fans
Supply air
Extract air
0,170 kW 1,25 A EC
0,170 kW 1,25 A EC
Post-heating
Liquid circulating radiator
Electrical connection
230 V, 50 Hz, 14,5 A power plug
Pre-heating
–
Enclosure protection class
IP34
Additional heating
Electrical resistor, 3000 W
Heat recovery bypass
Automatic
Filters
Supply air
Extract air
ISO Coarse > 75 % + ISO ePM₁
ISO Coarse > 75 %
Specific energy consumption (SEC)
in a cold climate
in a temperate climate
A+
A
Operating efficiencies
Annual efficiency
Supply air efficiency
Specific Fan Power (SFP)
75 % A+
87,6 %
0,59 kW (150 dm
3
/s) A++
Dimensions
(w x h x d)
1038 x 1241 x 773 mm
Weight
210 kg