External electrical connection

Measuring and adjusting performance values

Standard ventilation 

The volume flow rate of the air inside the cooker hood is measured 

with the damper closed and, where required, adjusted based on 

the static pressure loss and the performance scheme of the cooker 

hood. 

•  The static pressure loss is measured from the hole in the damper  

using the measuring tube found in the accessory bag (see figure). 

•  Determine the volume flow rate from 

the performance scheme based 

on the measured pressure and the 

number of open holes in the damper. 

Adjustment:

•  Cover the required number of holes 

in the damper with the magnetic 

strip that is delivered with the cooker 

hood.

 dp 

Boost ventilation

The volume flow rate of the air inside the cooker hood is measured 

with the damper open based on the static pressure loss and the 

performance scheme of the cooker 

hood. 

•  Measure the static pressure loss of 

the cooker hood. The measuring 

point must be located 2 times the 

duct diameter above the outlet 

collar of the cooker hood (see 

figure).

•  Determine the volume air flow 

based on the measured pressure 

and the performance scheme (with the damper open).

2

3

4

5

6

7

8 9

20

30

40

50

60 70

10

20

30

40

50

60

70

80

90

200

300

400

10

100

7

4

6

5

3

45

40

35

30

25

2

45

8

40

35

30

25

Air flow, dm³/s

Static pressure loss Pa

Damper open

Adjustment position 

L

pA

, dB(A)

Standard ventilation  

(settings 2-8)

 dp 

Measuring point,  

min. 2 x duct diameter

Vallox Oy | Myllykyläntie 9-11 | 32200 LOIMAA | FINLAND | www.vallox.com 

Customer S358 10 7732 200 | Afte358 10 7732 270

ALARM

TACHO

GND

0-11V

+  -

IN OUT

IN OUT

FIRE

ALARM

  RS 485
A  B GND

N

L

DAMPER

1    2    3

LIGHT

N    L

FAN

N    L

L

External feed based on 

the position of the hood 

damper. 

230VAC/4A

Terminal box on top of the hood

N

LA

L*

DAMP

IN OUT

PE

HOUSE 

AUTOMATION 

POSITION OF  THE DAMPER 

GUARD 

FUNCTION 

3 POTENTIAL FREE 

CONTACT DATA 

24VDC/5A

MODE

PIEZO

CONTACT DATA:

GUARD FUNCTION:

NORMAL SITUATION = OPEN

ACTIVATED = CLOSED

HOUSE AUTOMATION:

NORMAL SITUATION = OPEN

ERROR SITUATION 

(HOOD OR VENTILATION UNIT) = CLOSED

ACTIVATED GUARD FUNCTION = FLASHING

POSITION OF THE DAMPER:

DAMPER CLOSED = CONTACT OPEN

DAMPER OPEN = CONTACT CLOSED 

STANDARD VENTILATION 

Damper closed

Setting

Holes open/

damper

2

2

3

3

4

4

5

5

6

6

7

7

8

8

Measuring tubes that leave at the of top the hood are intended to 

be connected to the smoke limiter that is sold as an accessory. If 

the assembly does not include a smoke limiter, the tubes are left 

unconnected. Separate air flow measurement instructions are 

delivered with the smoke limiter.