16
Circulation pump
Thermo DC 200
9
Circulation pump
ATTENTION:
For a correct switching on of the heating appliance an adequate
circulation of the cooling medium must be ensured before swit-
ching on.
The heating appliance is preferably to be equipped with Valeo circulation
pumps.
The water flow rate through the heat exchanger of the Thermo DC must
be more than 1,500 litres/hour. The system must be completely bled.
The triggering/activation of the circulation pump is not carried out by the
heating appliance. For this reason the coolant demand must be provi-
ded for at the vehicle.
10 Switching thresholds
Upper switching threshold: 75°C
Lower switching threshold: 68°C
NOTE:
For information about these circulating pumps and
their installation, see http://www.valeo-thermal-
bus.com/eu_en/Products/Pumps