Trouble shooting 

 

 

*

On the IHP24 keyboard push: Error. 

 

Travel time open* 

 

Travel time close* 

 

 
If travel time is less than 10 sec 

1.

 

Slow down the system. 

 

2.1

 

Test valve configuration 

By manual calibration visually confirm that the actuator is operational. Also verify stay-put state. 
 
Push Calibration 

2.Manual 

 

Actuator can open 

 

Actuator can close 

 

Actuator can stay-put 

 

2.2

 

Test the position feedback 

By manual calibration operate the actuator, and note the ADC values shown on the screen. 
 
Push Calibration 

2.Manual 

 

ADC value at open 

 

ADC value at approx. 
50% travel 

 

ADC value at close 

 

 
If both values are less than 100: 

1.

 

Check that the IHP24 is configured with correct position input. 

2.

 

Check sensor wiring 

3.

 

Check if the 4-20mA sensor is active or passive. Active sensors require special wiring: See 
IHP24 manual and sensor manual. 

 
For a 4-20mA position loop feedback. If one value is less than 2600. 

1.

 

Adjust the positon sensor to operate within 4-20mA range. See sensor manual 

Actuator is operational 

 

Auto calibration 
sequence successful 

 

Errors in the error log

 

Содержание IHP24

Страница 1: ...DHP UM 026 Val Controls A S Limfjordsvej 3 DK 6715 Esbjerg N Tel 45 7547 0600 Fax 45 7547 0611 vc valcontrols com www valcontrols com Revision 2 1 7 IHP24 Troubleshooting ...

Страница 2: ...Esbjerg N Tel 45 7547 0600 Fax 45 7547 0611 vc valcontrols com www valcontrols com Revision 2 2 7 Table of contents 1 Identification 3 2 Basic trouble shooting 4 2 1 Valve configuration 4 2 2 Position feedback 4 2 3 Control loop 5 2 4 Transmitter loop 5 ...

Страница 3: ...ct information Name Company Phone Mail Nos are printed on device name plate Software ID Software version On the IHP24 keyboard push Status 2 Identification System information Actuator type Hydraulic Pneumatic Rotary Linear Position sensor mounted on the actuator 4 20mA passive 4 20mA active Potentiometer Sensor model only for 4 20mA Problem description Model no Serial no ...

Страница 4: ...can stay put 2 2 Test the position feedback By manual calibration operate the actuator and note the ADC values shown on the screen Push Calibration 2 Manual ADC value at open ADC value at approx 50 travel ADC value at close If both values are less than 100 1 Check that the IHP24 is configured with correct position input 2 Check sensor wiring 3 Check if the 4 20mA sensor is active or passive Active...

Страница 5: ...rator Push Status 1 Live status and push down arrow down until SP mA is shown From DCS or loop calibrator IHP24 Live menu SP mA 4mA 20mA If signals are 0 mA 1 Check wiring If 4 mA and 20 mA signals are off 1 Perform a signal calibration of AI0 Control loop See IHP24 manual 2 4 Test the transmitter loop AO0 Verify that the position signal transmitted from the IHP24 and the position signal received ...

Страница 6: ...S Limfjordsvej 3 DK 6715 Esbjerg N Tel 45 7547 0600 Fax 45 7547 0611 vc valcontrols com www valcontrols com Revision 2 6 7 If 4 mA and 20mA signals are off 2 Perform a signal calibration of the transmitter loop See IHP24 manual ...

Страница 7: ...the IHP24 through ValConnect export the configuration and mail it to Val Controls 3 2 4 20mA loop When troubleshooting a 4 20 mA loop it is generally a good idea to 1 Break the loop 2 Connect a loop calibrator to the position transmitter and verify that a signal is transmitted 3 Connect a loop calibrator to the receiver and verify that a signal is measured 3 3 Factory reset If troubleshooting does...

Отзывы: