5.3
Live Status
Register Len Access
Type
Name
Parameter Range/Units/Notes
Position
40300
1 RO
U16
Position - travel
Range: 0-10000
Divider: 100
Unit: %
Description: Position in %. For
switches 0% and 100% are shown
Device state
40421
1 RO
U16
Valve test service
Range: 00001: None; 00002: Auto
Calibration; 00003: PST; 00004: FST;
00005: SOT; 00006: ESD;
Description: Shows what test service
the device is running, e.g. partial
stroke test or auto calibration
40303
1 RO
U16
Remote/local switch status
Range: 00001: Local; 00002: Remote;
40304
1 RO
U16
Ready to reset
Range: 00001: Yes; 00002: No;
ESD signal status
40212
1 RO
U16
PS1 power line status
Range: 00001: On; 00002: Off;
Description: PS1 power line status
40210
1 RO
U16
PS3 power line status
Range: 00001: On; 00002: Off;
Description: PS3 power line status
40211
1 RO
U16
DO11
Range: 00001: On; 00002: Off;
Description: Power on DO11
40219
1 RO
U16
DO12
Range: 00001: On; 00002: Off;
Description: Power on DO12
40217
1 RO
U16
Is in ESD mode
Range: 00001: Yes; 00002: No;
Description: The device is in
emergency shutdown
Scheduler
44103
1 RO
U16
Action required?
Range:
00001: Yes;
00002: No;
Divider: 1
Description: A flag used in semi auto
to indicate that an action must be
performed
Digital Inputs
40221
1 RO
U16
DI1
Default: 00002
Range: 00001: On; 00002: Off;
Description: Current state of the input
40222
1 RO
U16
DI2
Default: 00002
Range: 00001: On; 00002: Off;
Description: Current state of the input
40223
1 RO
U16
DI3
Default: 00002
Range: 00001: On; 00002: Off;
Description: Current state of the input
40224
1 RO
U16
DI4
Default: 00002
Range: 00001: On; 00002: Off;
Description: Current state of the input
40225
1 RO
U16
DI5
Default: 00002
Range: 00001: On; 00002: Off;
Description: Current state of the input
40226
1 RO
U16
DI6
Default: 00002
Range: 00001: On; 00002: Off;
Description: Current state of the input
40227
1 RO
U16
DI7
Default: 00002
Range: 00001: On; 00002: Off;
Description: Current state of the input
40228
1 RO
U16
DI8
Default: 00002