Example
>sethea active 1
ACTIVE = 1
TOS = 4.00
THYS = 1.00
>
4.3.10 GETHEA
The
GETHEA
command displays the current heating status and temperature.
GETHEA<cr>
Example
>gethea
Heating OFF
Temperature 14.25
>
4.3.11 SETALR
WAC155 monitors wind sensor movement to detect if the sensors appear to be stuck in place.
To configure this functionality, use the
SETALR
command.
If
SETALR
is activated and parameters
dir
,
spd
, and
calm
are set to other value than 0, the
sensors are cross-checked for movement. If one sensor moves and the other does not for a
certain period of time, the motionless sensor is considered stuck.
SETALR [active] [dir] [spd] [calm] [dirlimit] [spdlimit] [sdpvoltlimit]
[dirvoltlimit] <value><cr>
active
Enables the diagnostics for wind sensor movement, 0 or 1. Default value:
0.
dir
Timeout for wind direction change in seconds. Range: 0 ... 256. Default
value: 60.
spd
Timeout for wind speed change in seconds. Range: 0 ... 256. Default
value: 60.
calm
Calm timeout in minutes. Defines how long both sensors may be static
until considered stuck. Range: 0 ... 65535. Default value: 1440.
Chapter 4 – Operation
41