stopbits
Number of stop bits, 1 or 2. Default value : 1.
txddelay
RS-485 turnaround delay in milliseconds. Range: 0 … 200. Default value:
30.
value
Value for the option
Example
>setcom baudrate 19200
BAUDRATE = 19200
DATABITS = 8
PARITY = NONE
STOPBITS = 1
TXDDELAY = 30
>
4.3.9 SETHEA
The
SETHEA
command configures the wind sensor heating control. Sensor heating ensures
frictionless rotation of sensor bearings in temperatures below -40 °C (-40°F). Heaters are
powered by a separate, external power supply. Heating is not enabled by default.
SETHEA [active] [tos] [thys] <value><cr>
active
Enables the wind sensor heating function. Possible values: 0 = Disabled
(default), 1 = Enabled, 2 = Forced ON
tos
Control limit for heating in Celsius degrees. Range: -55 … +125 (default: 4)
thys
Thermal hysteresis in Celsius degrees. Range: -55 … +125 (default: 1)
value
Value for the option
If heating is enabled, it turns on when the temperature drops below
TOS - THYS
. Heating
turns off when the temperature rises above
TOS + THYS
. With the default values of
TOS
=4
and
THYS
=1, heating is enabled at +3 °C and disabled at +5 °C.
SETHEA ACTIVE 2
is for testing purposes only. Leaving forced
heating on for longer periods of time may damage the heating elements of the
sensors.
CAUTION!
WAC155 User Guide