A.1.2 Configuration Registers
Table 14 Modbus Configuration Data Registers (Writable)
Register
Number
(Decimal)
Address
(Hexadecimal)
Register Description
Data Format
Unit / Valid Range
Environmental Compensation
769
0300
hex
Power-up value for
pressure compensation
32-bit float
hPa
Range: 450 … 1550
Init/default: 1013.25
771
0302
hex
Power-up value for
temperature
compensation
32-bit float
°C
Range: -10 … 70
Init/default: 25
773
0304
hex
Volatile pressure
compensation (value
cleared at probe reset)
32-bit float
hPa
Range 450 ... 1550
hPa
Init/default: 1013.25
775
0306
hex
Volatile temperature
compensation (value
cleared at probe reset)
32-bit float
°C
Range: -10 … 70
Init/default: 25
Function Control
1281
0500
hex
Pressure compensation
mode selection
Enum
0
= Off
1
= Setpoint
2
= External
1282
0501
hex
Temperature
compensation mode
selection
Enum
0
= Off
1
= Setpoint
2
= Measured
3
= External
1283
0502
hex
Installation type selection Enum
0
= Directly in
process
1
= Flow-
through adapter
Communication
1537
0600
hex
Serial address
16-bit integer
Valid range 1 …
255
Default: 240
MGP261 User Guide
M212273EN-A
70
Содержание MGP261
Страница 8: ...MGP261 User Guide M212273EN A 6...
Страница 50: ...4 Store the setting with Save MGP261 User Guide M212273EN A 48...
Страница 86: ...MGP261 User Guide M212273EN A 84...
Страница 88: ...MGP261 User Guide M212273EN A 86...
Страница 89: ......
Страница 90: ...www vaisala com...