To define a single setpoint for relay activation:
1. Open the
Settings > Relays
menu in the wireless configuration interface.
2. In the
Relays
menu, select the relay activation mode from the
Output Mode
dropdown
menu:
a. select
Active above trigger level
if you want the relay to activate when the probe
measurement exceeds the set limit
b. select
Active below trigger level
if you want the relay to activate when the probe
measurement falls below the set limit
3. Select the measurement parameter that is used to control the relay with the
Parameter
dropdown.
4. Set the unit of the measurement parameter with the
Unit
dropdown.
5. Enter the same measurement limit to both the
Low Trigger Level
and the
High Trigger
Level
field.
With this configuration, there is no hysteresis. The relay activates or switches off
immediately after passing this point.
6. Select the
Error State
for the relay.
6.3 Setting Relay Activation Limit Using
Hysteresis
If the measurement you are using to control the relay is likely to move back and forth close
to the activation setpoint, you can set a hysteresis that prevents the relay switching on and
off too frequently.
When hysteresis is used, the relay activates at the defined limit, but does not switch off
immediately when the measurement moves back to the other side of the activation limit.
Instead, with hysteresis, the relay remains active until the measurement reaches the defined
tolerated variation limit.
To set a relay activation limit with hysteresis:
1. Open the
Settings > Relays
menu in the wireless configuration interface.
2. In the
Relays
menu, select the relay activation mode from the
Output Mode
dropdown
menu:
a. select
Active above trigger level
if you want the relay to activate when the probe
measurement exceeds a set limit
b. select
Active below trigger level
if you want the relay to activate when the probe
measurement falls below a set limit
Chapter 6 – Configuring Relays
43
Содержание Indigo 202
Страница 1: ...M211966EN A User Guide Indigo 202 Digital Transmitter Indigo 202...
Страница 22: ...Indigo 202 User Guide M211966EN A 20...
Страница 62: ...Indigo 202 User Guide M211966EN A 60...
Страница 70: ...Indigo 202 User Guide M211966EN A 68...
Страница 74: ...Indigo 202 User Guide M211966EN A 72...
Страница 75: ......
Страница 76: ...www vaisala com...