Chapter 4 ________________________________________________________________ Operation
VAISALA ______________________________________________________________________ 111
Analog Output Fault Indication Setting
Factory default state for analog outputs during error condition is 0 V/
0 mA. Please be careful when selecting the new error value. The error
state of the transmitter should not cause unexpected problems in process
monitoring.
Use the display/keypad to set the analog output fault indication.
1. Open
the
MAIN MENU
by pressing any of the
▲▼◄►
arrow
buttons.
2. Select
Interfaces
by pressing the
►
arrow button.
3. Select
Analog Outputs
by pressing the
►
arrow button.
4. Select
Output 1/2/3
by pressing the
►
arrow button.
5. Select
Fault indication
. Press
SET
to confirm your selection.
Enter the fault indication value by using the arrow buttons. Press
OK
to confirm your setting. This value is outputted if a transmitter
error occurs.
6. Press
EXIT
to return to the basic display.
AERR
Use the serial line
AERR
command to change the error output.
AERR
Example:
>aerr
Ch1 error out : 0.000V ? 5.0
Ch2 error out : 0.000V ? 5.0
>
NOTE
The error output value must be within a valid range for the output type.
NOTE
The error output value is displayed only when there are minor electrical
faults such as a humidity sensor damage. When there is a severe device
malfunction, the error output value is not necessarily shown.