Chapter 5 _______________________________________________________________ Diagnostics
VAISALA_______________________________________________________________________ 85
REMOTE OBJECT MONITOR FAULT OR
ERROR REASON FOR SWITCHOVER
DETECTED BY SERVER X
This message indicates that:
-
Remote Object Monitor process is not running in the CDU.
-
or Remote Object Monitor process has detected an error in the CDU
(for example, an obligatory process is missing).
To find out the cause and solve the problem, do the following on the RCM
workstation:
1.
In the Diagnostics application, check if the Remote Object Monitor
process is in the
Missing processes
list. If it is missing, continue from
section
Restarting a Process on page 87
.
2.
If the process is not missing, the Remote Object Monitor process has
detected an error in the CDU and has made an automatic switch-over.
To find out more about the reason (for example, an obligatory process
or time synchronization is missing), see the other events in the
Events
panel.
Dealing with Operational Event Messages
(OPER)
Operational event messages include the following two message types:
-
Messages related to sensor measurement problems
-
Messages related to changes in weather
Sensor-related messages appear when the data measured by a sensor does
not fall within the range specified for that sensor (for example, “WIND
SPEED 52, MINIMUM 0.0, MAXIMUM 50.0”). These messages can
indicate, for instance, that the sensor needs calibration or that there is a
physical obstruction preventing the normal operation of the sensor.
Weather-related messages appear, for instance, when wind values are
changing as preconfigured.