Appendix
80
Installation and maintenance instructions aroTHERM 0020257297_02
Technical data
–
Application limits, cooling mode
Applicability:
Product with cooling mode
VWL 35/5
AS 230V
(S2)
VWL 55/5
AS 230V
(S2)
VWL 75/5
AS 230V
(S2)
VWL 105/5
AS 230V
(S2)
VWL 105/5
AS (S2)
VWL 125/5
AS 230V
(S2)
VWL 125/5
AS (S2)
Air temperature, minimum
15
℃
15
℃
15
℃
15
℃
15
℃
15
℃
15
℃
Air temperature, maximum
46
℃
46
℃
46
℃
46
℃
46
℃
46
℃
46
℃
Technical data
–
Power, heating mode
VWL 35/5
AS 230V
(S2)
VWL 55/5
AS 230V
(S2)
VWL 75/5
AS 230V
(S2)
VWL 105/5
AS 230V
(S2)
VWL 105/5
AS (S2)
VWL 125/5
AS 230V
(S2)
VWL 125/5
AS (S2)
Heating output, A2/W35
2.50 kW
3.40 kW
4.60 kW
8.30 kW
8.30 kW
8.30 kW
8.30 kW
Coefficient of performance,
COP, EN 14511, A2/W35
3.80
3.80
3.80
3.90
3.90
3.70
3.70
Power consumption, effect-
ive, A2/W35
0.66 kW
0.89 kW
1.21 kW
2.13 kW
2.13 kW
2.24 kW
2.24 kW
Power consumption, A2/W35
3.20 A
4.40 A
5.50 A
10.20 A
3.30 A
10.50 A
3.40 A
Heating output, A7/W35
3.20 kW
4.50 kW
5.80 kW
9.80 kW
9.80 kW
10.30 kW
10.30 kW
Coefficient of performance,
COP, EN 14511, A7/W35
5.00
4.80
4.70
4.70
4.70
4.60
4.60
Power consumption, effect-
ive, A7/W35
0.64 kW
0.94 kW
1.23 kW
2.09 kW
2.09 kW
2.24 kW
2.24 kW
Power consumption, A7/W35
3.20 A
4.60 A
5.80 A
9.90 A
3.20 A
10.50 A
3.50 A
Heating output, A7/W45
3.10 kW
4.10 kW
5.50 kW
9.10 kW
9.10 kW
9.70 kW
9.70 kW
Coefficient of performance,
COP, EN 14511, A7/W45
3.60
3.50
3.60
3.50
3.50
3.50
3.50
Power consumption, effect-
ive, A7/W45
0.86 kW
1.17 kW
1.53 kW
2.60 kW
2.60 kW
2.77 kW
2.77 kW
Power consumption, A7/W45
4.10 A
5.40 A
6.80 A
12.00 A
4.10 A
12.70 A
4.30 A
Heating output, A7/W55
2.80 kW
3.70 kW
5.00 kW
10.40 kW
10.40 kW
11.00 kW
11.00 kW
Coefficient of performance,
COP, EN 14511, A7/W55
2.60
2.70
2.70
2.80
2.80
2.80
2.80
Power consumption, effect-
ive, A7/W55
1.08 kW
1.37 kW
1.85 kW
3.71 kW
3.71 kW
3.93 kW
3.93 kW
Power consumption, A7/W55
4.90 A
6.30 A
8.00 A
17.00 A
5.80 A
18.30 A
6.20 A
Heat output, A-7/W35
3.60 kW
4.90 kW
6.70 kW
10.20 kW
10.20 kW
11.90 kW
11.90 kW
Coefficient of performance,
COP, EN 14511, A-7/W35
3.20
2.70
2.70
2.80
2.80
2.50
2.50
Power consumption, effect-
ive, A-7/W35
1.13 kW
1.81 kW
2.48 kW
3.64 kW
3.64 kW
4.76 kW
4.76 kW
Power consumption, A-
7/W35
5.40 A
8.60 A
11.80 A
17.40 A
5.70 A
22.70 A
7.50 A
Heat output, A-7/W35, noise
reduction mode 40%
3.20 kW
3.20 kW
4.20 kW
7.50 kW
7.50 kW
7.50 kW
7.50 kW
Coefficient of performance,
COP, EN 14511, A-7/W35,
noise reduction mode 40%
3.10
3.10
3.10
2.90
2.90
2.90
2.90
Heat output, A-7/W35, noise
reduction mode 50%
2.70 kW
2.70 kW
3.50 kW
6.30 kW
6.30 kW
6.30 kW
6.30 kW
Coefficient of performance,
COP, EN 14511, A-7/W35,
noise reduction mode 50%
3.20
3.20
3.20
3.00
3.00
3.00
3.00
Heat output, A-7/W35, noise
reduction mode 60%
2.20 kW
2.20 kW
2.80 kW
5.10 kW
5.10 kW
5.10 kW
5.10 kW
Coefficient of performance,
COP, EN 14511, A-7/W35,
noise reduction mode 60%
3.20
3.20
3.20
2.90
2.90
2.90
2.90