6 Electrical installation
68
Installation and maintenance instructions aroTHERM 0020257297_02
Case
Connection type
Energy supply company lockout not
provided
Single power supply
Energy supply company lockout
provided, shutdown via connection
S21
Energy supply company lockout
provided, shutdown via partition
Dual power supply
6.6.1
1~/230V, single power supply
1.
If it is stipulated for the installation site, install one resid-
ual-current circuit breaker for the product.
N
L
1
2
3
4
5
1
2
L
N
L1
L2
L3
N
L
N
X211
X210
X200
4
2
3
1
2.
Install one electrical partition for the product (circuit
breaker), as shown in the illustration.
3.
Use one 3-pole power supply cable.
4.
Route the power supply cable from the building and
through the wall duct to the product.
5.
Strip the outer sheathing from the electrical wire.
(
→
Page 67)
6.
Connect the power supply cable to connection
X200
in
the electronics box.
7.
Use the strain relief clamp to secure the power supply
cable in place.
6.6.2
1~/230V, dual power supply
1.
If it is stipulated for the installation site, install two resid-
ual-current circuit breakers for the product.
N
L
1
2
3
4
5
L1
L2
L3
N
X211
X210
X200
N
L
1
2
L
N
L
N
4
2
3
1
2.
Install two electrical partitions for the product (circuit
breaker), as shown in the illustration.
3.
Use two 3-pole power supply cables.
4.
Route the power supply cables from the building and
through the wall duct to the product.
5.
Strip the outer sheathing from the electrical wire.
(
→
Page 67)
6.
Connect the power supply cable (from the heat pump
electricity meter) to connection
X200
in the electronics
box.
7.
Remove the 2-pole bridge from the
X210
connection.
8.
Connect the power supply cable (from the household
electricity meter) to connection
X211
.
9.
Use the strain relief clamps to secure the power supply
cables in place.
6.7
Establishing the power supply, 3~/400V
Caution.
Risk of material damage due to high con-
nected voltage.
At mains voltages greater than 440 V, elec-
tronic components may be damaged.
▶
Ensure that the nominal voltage of the 3-
phase mains is 400 V (+10%/-15%).
Caution.
Risk of material damage due to large
voltage difference.
If the voltage difference between the indi-
vidual power supply phases is too large, this
can lead to the product malfunctioning.
▶
Ensure that the voltage difference
between the individual phases is below
2%.
▶
Determine the type of connection:
Case
Connection type
Energy supply company lockout not
provided
Single power supply
Energy supply company lockout
provided, shutdown via connection
S21
Energy supply company lockout
provided, shutdown via partition
Dual power supply
6.7.1
3~/400V, single power supply
1.
If it is stipulated for the installation site, install one resid-
ual-current circuit breaker for the product.