background image

Manual - Solar hot water systems

52

8

6a 6b

15

14

13

12

1

2

5

3

20

19

10

9

21

11

Fig. 6.1  Start-up of the total system

Flushing and filling the solar circuit and subjecting it to 

a hydraulic pressure test

Flushing is performed from the solar pump unit to the 
cylinder via the collector. This is how to do it:
•  Open the fill/vent valve (

1

) and connect the filling 

pump to the fill/vent valve (

1

).

•  Place the three-way ball valve (

15

) into flush position.

•  Connect the drain hose of the Vaillant filling pump or a 

similar hose with filter (

9

) to the fill/drain valve (

12

). 

Put the other end into the solar fluid container (

10

).

•  Pump in solar fluid from the container by the filling 

pump (

19

) via the fill/drain valve (

1

), so that the solar 

fluid from fill/drain valve (

12

) is filtered and flows back 

into the container.

•  To flush and filter the solar circuit, pump circularly for 

10 minutes. Monitor the filter and clean it if necessary.

A self-priming pump with a pressure of 2 to 3 bar is 
required

 

to fill the solar circuit. This is how to do it (see 

Fig. 6.1):
•  After flushing close the fill/drain valve (

12

) and pump 

in solar fluid once a pressure of 1.7 bar is achieved.

•  Close the fill/vent valve (

1

) too and place the three-

way ball valve (

15

) into circulation position.

•  Switch off the filling pump and switch on the solar 

pump (

13

) to allow air bubbles to escape via the 

bleeder.

•  Block the gravity brakes (

8

 and 

14

) (position 45°) to 

discharge the remaining air.

•  When bleeding is completed release the gravity brakes.

Collector circuit filling pressure

The filling pressure Pa should be approx. 0.5 bar over 
the static pressure Pstat.
Pa = h x 0.1 + 0.5 bar

6.2 

Setting the flow rate and pump

0,

5

1

2

3

0,

5

1

2

3

4

5

6

4

5

6

L/

min

L/
min

1,1 l/min

1

2

Fig. 6.2 Setting the flow rate

The 3-speed circulating pump can be fine-tuned to 
adjust the flow rate to the collector's performance.

h

 Note!

We recommend a value of 0.66 l/min per m

collector surface area.

This is how to do it:

 

Use Table 6.1 to calculate the flow rate to be set by 
multiplying the installed collector surface area with 
the value of 0.66 l/m

• min.

•  Set the pump speed to roughly set the flow rate.

 

Use an Allen key to finely adjust the flow rate at the 
adjustment valve (see Fig. 6.2 Pos. 

1

).

The adjusted flow rate can be viewed on the display (

2

).

Table 6.1 and 6.2 provide reference values for possible 
pump speeds depending on the collector connection and 
pipe length and cross-section.

If you use auroMATIC 560 solar control, the flow rate 
can be used to calculate the gain. To make an accurate 
calculation, the flow rate must be entered on the 
controller. You can find further information in the 
operating and installation manual of the control.

6 Start-up

Содержание Solar hot water systems

Страница 1: ...For the installer owner Start up maintenance and troubleshooting manual notes for the operator Solar System and auroSTOR unvented solar cylinder Solar hot water systems GB...

Страница 2: ...o the solar pump unit 31 5 3 5 Bleeding of the solar circuit 32 5 4 Installation of the reheating circuit piping 32 5 5 Installation of the hot water pipework 32 5 5 1 Hot water thermostatic mixing va...

Страница 3: ...tric shock e Danger Risk of burns or scalding a Caution Potentially dangerous situation for the product and environment h Note Application recommendation Symbol for a required task 2 Overview of stand...

Страница 4: ...nstructions The entire solar system must always be installed and operated in accordance with recognised technical standards d Danger Risk of falling Make sure you adhere to the valid work protection r...

Страница 5: ...the maintenance and inspection conditions a Caution We accept no liability for any damage or injuries caused by failure to observe this manual At the end of this manual is a start up protocol which sh...

Страница 6: ...alve supplied together with the solar cylinder 4 Immersion heater 5 230 V motorised 2 port valve supplied together with the boiler 6 auroTHERM collector 7 Solar pump unit 8 Protection vessel optional...

Страница 7: ...ter VR 65 can be used to wire up the system if an eBUS capable Vaillant boiler is used A standard wiring box can be used if a Vaillant boiler which is not eBUS capable or an external boiler is used Co...

Страница 8: ...collector tubes with internal mirror of pure silver and glass glass connection of sleeve and absorber pipe for lasting vacuum sealing the collector ensures constant high performance over its entire s...

Страница 9: ...prEN 12975 2 c 1 m s in the glass tube C 250 250 Shutdown temperature according to prEN 12975 2 c 1 m s at the collector connection C 180 180 Efficiency 0 according to EN 12975 78 3 78 3 Efficiency c...

Страница 10: ...area gross aperture net m2 2 24 2 02 Height mm 1930 Width mm 1160 Depth mm 110 Weight kg 43 Absorber capacity l 1 1 Copper pipe connection flat face mm G 1 2 Insulation thickness mm 60 Max operating...

Страница 11: ...ontrol pack consisting of an expansion relief valve 1 and a pressure gauge 2 for visual inspections 4 2 3 Solar expansion vessel The solar expansion vessel 4 is used to equalise the pressure while the...

Страница 12: ...essential component of the solar system To achieve optimum heat transfer you must achieve a certain flow rate which is referred to as the nominal flow rate refer to Section 6 2 Setting the flow rate...

Страница 13: ...eat exchanger reheating circuit 3 7 VIH S GB 250 S heat exchanger reheating circuit 3 7 VIH S GB 300 S heat exchanger reheating circuit 3 7 Solar pump unit 0 9 auroTHERM exclusive VTK 550 3 56 auroTHE...

Страница 14: ...r must be disposed of according to local official regulations 6 Measures to be taken if substances are released accidentally 6 1 Individual related measures No particular measures required 6 2 Environ...

Страница 15: ...components 12 3 Persistence and biodegradability information on elimination OECD 301 A test method new version Analysis method DOC acceptance Degree of elimination 70 28 d Assessment easily biodegrad...

Страница 16: ...ferences not absolute temperature values are important for the operation of solar systems That is why solar systems are controlled by what is referred to as temperature difference controllers Temperat...

Страница 17: ...dditional functions including central heating override and the time control function of an additional circulation pump For wiring refer to Section 5 8 Electrical installation and the operating and ins...

Страница 18: ...ng bar long for 2 x VTK 550 1 1 2 2 Mounting bar normal for 1 x VTK 550 1 1 Mounting bar short for 1 x VTK 275 1 Roof bracket set for 2 x VTK 550 1 1 2 2 Roof bracket set for 1 x VTK 550 or 1 x VTK 27...

Страница 19: ...1 1 Solar pump unit 1 1 1 1 Expansion vessel 25 l 1 1 Expansion vessel 35 l 1 1 Protection vessel for expansion vessel 1 1 1 1 Automatic air separator 1 1 1 1 Thermostat mixer 1 1 1 1 Solar control au...

Страница 20: ...te tiles qty 6 1 On roof kit for two panels 1 Stainless steel connection pipe DN12 2x1m 1 Single insulated tube DN16 length 15m 2 Fittings pack for DN16 tube 1 Solar pump unit 1 Expansion vessel 18 li...

Страница 21: ...collector solar set Item no 0020036552 Thermostatic mixing valve 1 Solar control auroMATIC 560 1 NTC sensor VR10 solar gain 1 Solar fluid 20 litre 2 Table 5 2 Scope of delivery of the auroTHERM flat...

Страница 22: ...dish 1 1 1 Motorised 2 port valve A B 1 1 1 DHW expansion vessel 18 l 1 DHW expansion vessel 25 l 1 1 Mounting bracket for expansion vessel 1 1 1 Carrier handle 1 1 1 Compression fittings 1 1 1 Drain...

Страница 23: ...ansion relief valve one port valve 6 0 bar 10 Tundish 11 Cylinder drain valve 12 Sp 2 temperature sensor immersion sleeve 13 Adjustable feet 14 Return solar circuit 15 Flow solar circuit 16 Return boi...

Страница 24: ...t out TCO refer to Section 5 8 Electrical installation It ensures the solar pump is switched off if the hot water temperature in the cylinder rises above 90 C Fig 5 2 Attachment of the solar pump TCO...

Страница 25: ...ection 22 mm pressure pipe Pressure controlled cold water outlet 22 mm pressure pipe Secondary return Inches G 3 4 Flow boiler solar circuit 22 mm pressure pipe Return boiler solar circuit 22 mm press...

Страница 26: ...system Flow out litres min of the system 10 10 0 Fig 5 5 auroSTOR hot water flow rates at 60 C Static operating pressure of the cold water supply The displayed flow rates apply to installations in whi...

Страница 27: ...isolate the primary heat source in the event of failure of the domestic water thermostat 5 1 6 Safety instructions and regulations This product has been checked for adherence to the building regulatio...

Страница 28: ...ransport A cylinder carrier handle is supplied to make the transport to the installation site easier 1 Fig 5 7 Fastening the cylinder carrier handle Fasten the carrier handle 1 to the hot water connec...

Страница 29: ...re and pressure relief valve 3 Immersion heater 4 Solar circuit flow Cylinder type A B C d A F g h R VIH S GB 200 S 1468 1499 454 384 314 589 1118 813 953 VIH S GB 250 S 1758 1789 454 384 314 589 1408...

Страница 30: ...orised 2 port valve supplied with the solar cylinder 4 Immersion heater 5 230 V motorised 2 port valve supplied with the boiler 6 auroTHERM collector 7 Solar pump unit 8 Protection vessel optional 9 S...

Страница 31: ...tion Risk of damage to the collectors due to excessive pressure The installation of a motorised 2 port valve in the pipes of the solar system is not allowed since the safety devices in the solar circu...

Страница 32: ...MAX pro with open ventilation have an installed circulating pump it is not necessary to install them An appropriate pump must be installed in the reheating circuit if the solar cylinder is used with a...

Страница 33: ...water of 10 C if the measured static cold mains water pressure is 2 bar and the available flow rate 30 l min The solar cylinder operates satisfactorily at a mains water pressure of below 2 bar but at...

Страница 34: ...reas with high water pressure 4 bar or more a bath or shower mixer valve can also be connected to the pressure controlled cold water connection 4 Fig 5 16 of the water control pack to ensure the press...

Страница 35: ...no risk of anyone coming in contact with hot water A suitable point is for example under a fixed grating above the trap of a trapped gully Low discharge pipes for example up to 100 mm above external...

Страница 36: ...e solar cylinder for potential equalisation 5 8 1 Immersion heater The auroSTOR VIH S GB 200 300 S solar cylinders have been equipped with an immersion heater by the manufacturer 1 2 4 5 3 230 V AC 3...

Страница 37: ...the immersion heater You can find a wiring sheme on the inside of the cylinder cover 5 8 3 Combination options of the control components Boiler used eBUS capable boiler such as the Vaillant ecoTEC or...

Страница 38: ...ring schemes 2 or 4 1 2 3 N L 1 7 2 10 3 To wiring box 1 2 3 1 Fig 5 21 Electrical connection of the cylinder thermostat Wiring of the control components Wiring scheme 1 eBUS capable Vaillant boiler W...

Страница 39: ...e immersion heater solar cylinder and solar control fit properly in the immersion sleeves Connect the collector temperature sensor to terminal Kol 1 in the auroMATIC 560 solar control Establish the co...

Страница 40: ...Brown Grey Orange Earth Blue Brown Grey Orange Hot Water 2 Port Valve VR 65 DHW add terminal strip LEG BYP Central Heating 2 Port Valve VR 65 CH auroSTOR cylinder 3 amp fused supply Boiler terminal s...

Страница 41: ...nal SP 2 in the auroMATIC 560 solar control Attach the temperature sensor for the gain 2 to the return pipe of the solar circuit nearby the solar cylinder Connect this temperature sensor to the termin...

Страница 42: ...Valve Central Heating Programmer 230 V 230 V 230 V LP UV 1 LEG BYP VRS 560 solar control 230 V EP Coll NTC auroSTOR additional terminal strip auroSTOR cylinder TCO collector pump additional terminal s...

Страница 43: ...emperature sensor to terminal SP 1 in the auroMATIC 560 solar control Push a VR 10 temperature sensor 3 in the immersion sleeve for the bottom cylinder area Connect this temperature sensor to terminal...

Страница 44: ...get temperature if the solar system is not operating and if the hot water programmer is on h Note Programme the separate hot water programmer to provide hot water when required by the customer Conside...

Страница 45: ...mp Hot Water 2 Port Valve 3 amp fused supply 230 V any Vaillant boiler Central Heating 2 Port Valve Central Heating Programmer 230 V TCO collector pump VRS 560 solar control TCO and cyl thermostat aur...

Страница 46: ...ct this temperature sensor to terminal SP 2 in the auroMATIC 560 solar control Attach the temperature sensor for the gain 2 to the return pipe of the solar circuit nearby the solar cylinder Connect th...

Страница 47: ...iler Terminal Strip 230 V LP UV 1 additional terminal strip LEG BYP not used to 10 way wiring box NOT separate fused spur Central Heating 2 Port Valve 230 V Hot Water 2 Port Valve auroSTOR cylinder TC...

Страница 48: ...1 in the auroMATIC 560 solar control Push a VR 10 temperature sensor 3 in the immersion sleeve for the bottom cylinder area Connect this temperature sensor to terminal SP 2 in the auroMATIC 560 solar...

Страница 49: ...mer to provide hot water when required by the cus tomer Consider carefully when the solar system might be running and try to time to HW pro grammer to run when there is unlikely to be any solar gain h...

Страница 50: ...Heating Pump if not in boiler 230 V Collector Pump additional terminal strip LEG BYP TCO collector pump EP additional terminal strip auroSTOR cylinder Coll NTC auroSTOR TCO and cyl thermostat VRS 560...

Страница 51: ...er secondary circuit refer to Section 6 4 Set the hot water thermostatic mixing valve refer to Section 6 5 Fill the reheating circuit refer to Section 6 6 Use only Vaillant solar fluid item no 302 429...

Страница 52: ...Switch off the filling pump and switch on the solar pump 13 to allow air bubbles to escape via the bleeder Block the gravity brakes 8 and 14 position 45 to discharge the remaining air When bleeding i...

Страница 53: ...m2 min it results in a calculated flow rate of 1 6 l min which should be indicated by the flow rate meter see Fig 6 2 For the design and function of the flow rate meter refer to Section 4 5 Flow rate...

Страница 54: ...the motorised 2 port valve by setting it back to AUTO 2 1 1 2 3 N L immersion heater C cylinder control C Fig 6 4 Setting thermostats Set the knob of the hot water thermostat of the solar cylinder 2 F...

Страница 55: ...gain a Note In areas with hard water the set hot water temperature should not exceed 45 C to avoid calcification Go through the operating manuals with the owner and answer any questions Point out the...

Страница 56: ...nction on off automatic Annually Check the sensor temperature display Annually Secondary return reheating Check the circulation pump Annually Check the timer time programme settings Annually Reheating...

Страница 57: ...peed or unblock the rotor insert a screwdriver in the notch and turn it by hand 5 Pump dirty Dismantle the pump and clean it Close the flow rate meter and pump ball valve 6 Pump defective Replace the...

Страница 58: ...valve and replace it if necessary Pressure limiting valve defective Replace the pressure limiting valve Blockage in the system Unblock the blockage and replace any blocked parts Check the system for...

Страница 59: ...Dirt on the valve seat of the expansion relief valve Check the expansion relief valve and reset it manually Pressure limiting valve defective Switch off the boiler and immersion heater and check wheth...

Страница 60: ...ystem How to control the solar system is described in the manuals for each controller h Note In the event of leaks in the water pipework close the cold water stop valve at the cylinder immediately to...

Страница 61: ...clean the exterior of the solar cylinder with a damp cloth and a little soap a Caution Risk of damage Do not use any abrasives or solvents since they could damage the exterior or the connections 9 6...

Страница 62: ...er enough hot water Check whether the standby cylinder temperature has been set properly on the controller approx 60 C recommended Check the hot water thermostat mixer setting approx 60 C recommended...

Страница 63: ...fill vent valve checked for leaks retighten union nuts if necessary Temperature and pressure relief valve checked Stop valve for reheating source installed normally motorised 2 port valve Flow rate s...

Страница 64: ...gnation Serial number Boiler system type Open Closed Installation location of pressure limiting valve System values Hot water temperature at the nearest tap C Achievable maximum cylinder temperature C...

Страница 65: ...see installation manual of solar control C Switch on temperature difference Kelvin Switch off temperature difference Kelvin Other settings Important activated functions Name of the installer in block...

Страница 66: ...Manual Solar hot water systems 66 11 Start up protocol...

Страница 67: ...67 Manual Solar hot water systems Start up protocol 11...

Страница 68: ...0020009607_01 GB 012007...

Отзывы: