8
Installation and maintenance instructions ecoTEC sustain 0020253094_05
3
Technical data
Technical data
–
General
VUW 246/7-2 (H-
GB)
VUW 286/7-2 (H-
GB)
VUW 346/7-2 (H-
GB)
Gas category
II2H3P
II2H3P
II2H3P
Diameter of the gas pipe
1/2"
1/2"
1/2"
Diameter of the heating pipe
3/4"
3/4"
3/4"
Diameter of the domestic hot water
pipe
3/4"
3/4"
3/4"
Expansion relief valve connector
(min.)
15.0 mm
15.0 mm
15.0 mm
Condensate discharge pipe (min.)
21.5 mm
21.5 mm
21.5 mm
G20 gas supply pressure
2.0 kPa
(20.0 mbar)
2.0 kPa
(20.0 mbar)
2.0 kPa
(20.0 mbar)
G31 gas supply pressure
3.7 kPa
(37.0 mbar)
3.7 kPa
(37.0 mbar)
3.7 kPa
(37.0 mbar)
Gas flow at P max.
–
domestic hot
water (G20)
2.6 m
³
/h
3.0 m
³
/h
3.7 m
³
/h
CE number (PIN)
CE-0063CR3775
CE-0063CR3775
CE-0063CR3775
SAP 2009/2012 annual efficiency (%)
89.2
89.1
89.2
Flue gas mass flow rate in heating
mode at P min.
3.1 g/s
3.6 g/s
4.1 g/s
Flue gas mass flow rate in heating
mode at P max.
8.9 g/s
8.9 g/s
8.9 g/s
Flue gas mass flow rate in domestic
hot water mode at P max.
11.6 g/s
13.6 g/s
16.5 g/s
Released system types
C13, C33, C43, C53
C13, C33, C43, C53
C13, C33, C43, C53
Min. flue gas temperature
44
℃
41
℃
43
℃
Max. flue gas temperature
85
℃
95
℃
99
℃
Nominal efficiency at 80/60 °C
98.9 %
98.9 %
98.9 %
Nominal efficiency at 50/30 °C
107.5 %
107.3 %
106.6 %
Partial load nominal efficiency (30%)
107.4 %
108.0 %
108.1 %
NOx class
6
6
6
Product dimensions, width
440 mm
440 mm
440 mm
Product dimensions, depth
338 mm
338 mm
338 mm
Product dimensions, height
720 mm
720 mm
720 mm
Net weight
30.8 kg
30.8 kg
32.8 kg
Weight when filled with water
33.5 kg
33.5 kg
35.9 kg
Technical data
–
G20
VUW 246/7-2 (H-
GB)
VUW 286/7-2 (H-
GB)
VUW 346/7-2 (H-
GB)
Effective output range (P) at 50/30 °C
7.0 to 20.1 kW
8.0 to 20.1 kW
9.1 to 19.9 kW
Effective output range (P) at 80/60 °C
6.4 to 18.5 kW
7.4 to 18.5 kW
8.4 to 18.5 kW
Heat output range
–
domestic hot wa-
ter or cylinder reheating (P)
6.6 to 24.3 kW
7.5 to 28.1 kW
8.4 to 34.0 kW
Maximum heat input
–
heating (Q
max.)
18.7 kW
18.7 kW
18.7 kW
Minimum heat input
–
heating (Q min.)
6.6 kW
7.6 kW
8.6 kW
Maximum heat input
–
Domestic hot
water or cylinder reheating (Q max.)
24.4 kW
28.5 kW
34.6 kW
Minimum heat input
–
Domestic hot
water or cylinder reheating (Q min.)
6.6 kW
7.6 kW
8.6 kW
Содержание ecoTEC sustain 24
Страница 1: ...en Installation and maintenance instructions ecoTEC sustain 24 28 34 0020253094_05 04 11 2020...
Страница 61: ......
Страница 62: ......
Страница 63: ......