9 Inspection and maintenance
30
Installation and maintenance instructions ecoTEC plus 0020134823_07
3
4
▶
Undo the four screws on the flange connection
(3)
to the
gas valve assembly.
Condition
: Applies for 100 kW and 120 kW
3
4
▶
Undo the four screws on the flange connection
(3)
to the
gas valve assembly.
6.
Move the gas pipe
(4)
to the side.
8
9
10
11
13
5
6
7
12
11
8
10
12
5
6
7
9
13
806/5-5
1006/5-5
1206/5-5
Danger!
Risk of poisoning and fire caused by es-
caping gas!
The gas pipe may become damaged.
▶
Ensure that you do not damage the seals
on the gas pipe when removing and in-
stalling the gas-air mixture unit.
7.
Remove the ionisation line plug from the ionisation elec-
trode
(11)
, and remove the earth connection plug from
the earthing lug.
8.
Remove the ignition line plug and the earth connec-
tion for the ignition electrode
(9)
from the ignition trans-
former.
Note
The cable is firmly connected to the ignition
electrode.