7 Start-up
20
Installation and maintenance instructions ecoTEC plus 0020134823_07
7.5.6
Additional relay and multi-functional module
Additional components that are connected to the product can
be adjusted here. This setting can be changed using
D.027
and
D.028
.
7.5.7
Competent person telephone number
You can store your telephone number in the unit menu. The
end user can view the telephone number. The telephone
number can be up to 16 digits long and must not contain any
spaces.
7.5.8
Ending the installation assistant
Once the installation assistant has been completed and con-
firmed, it will not start up automatically next time the unit is
switched on.
7.6
Restarting the installation assistants
You can restart the installation assistant at any time by call-
ing it up in the menu.
Menu
→
Installer level
→
Start inst. assistant
7.7
Calling up unit configuration and
diagnostics menu
To recheck and reset the most important system parameters,
call up the
Unit configuration
.
Menu
→
Installer level Unit configuration
The setting options for more complex installations can be
found in the
Diagnostics menu
.
Menu
→
Installer level Diagnostics menu
7.8
Using check programmes
Menu
→
Installer level
→
Test programmes
→
Check pro-
grammes
By activating various check programmes, you can trigger
special functions on the product.
Display
Meaning
P.00
Purging check programme:
The boiler circulation pump is cyclically actuated.
The heating circuit is purged via the automatic air
vent.
1 x
: Start heating circuit purging
3 x
(
): Restart heating circuit purging
1 x
(
Cancel
): End purge programme
Note
The purge programme runs for 7.5 min per circuit
and then terminates.
Purging the heating circuit:
Actuating the external pump for 15 cycles: 15 s on,
10 s off. Display:
Active heating circuit
.
P.01
Maximum load check programme:
After successful ignition, the product is operated at
maximum heat input.
P.02
Minimum load check programme:
After successful ignition, the product is operated at
minimum heat input.
P.06
Filling mode check programme:
The burner and pump are switched off (to fill or drain
the product).
P.00 Purging
Cancel
Heating circuit
1,2 bar
Note
If the product is in error condition, you cannot start
any check programmes. You can detect an error
condition by the fault symbol shown in the left
bottom corner of the display. You must first reset.
To terminate the check programmes, you can press (
Can-
cel
) at any time.
7.9
Reading off the filling pressure
The product's supply pipe is equipped with an analogue
pressure gauge, a symbolic bar graph display and a digital
pressure gauge.
▶
To read off the digital filling pressure value, press the
button twice.
If the heating installation is full, in order to ensure that it op-
erates smoothly, the indicator on the pressure gauge must
point to the upper half of the grey area or to the middle of the
bar graph display on the display (marked by the dashed limit
values) when the heating installation is cold. This corres-
ponds to a filling pressure of between 0.1 MPa and 0.2 MPa
(1.0 bar and 2.0 bar).
If the heating installation extends over several storeys,
higher filling pressures may be required to avoid air entering
the heating installation.
7.10
Preventing low water pressure
To prevent damage to the boiler that is caused by a filling
pressure that is too low, the boiler is fitted with a water
pressure sensor. If the filling pressure falls below 0.1 MPa
(1.0 bar), the product indicates low pressure by displaying a
flashing pressure value. If the filling pressure falls below 0.05
MPa (0.5 bar), the product switches off. The display shows
F.22
.
▶
Top up the heating water to start the product up again.
The pressure value flashes in the display until a pressure of
0.11 MPa (1.1 bar) or higher has been reached.
▶
If you notice frequent drops in pressure, determine and
eliminate the cause.