8 Adapting the unit to the heating installation
20
Installation and maintenance instructions ecoFIT sustain 0020230529_04
8
Adapting the unit to the heating
installation
You can reset/change the system parameters.
Overview of diagnostics codes (
8.1
Setting the burner anti-cycling time
To prevent frequent switching on and off of the burner and
thus prevent energy losses, an electronic restart lockout
is activated for a specific period each time the burner is
switched off. The burner anti-cycling time is only active for
the heating mode. Domestic hot water mode during a burner
anti-cycling time does not affect the time function element.
8.1.1
Setting the burner anti-cycling time
1.
Navigate to diagnostics code
D.002
in the installer level
and confirm by pressing
.
2.
Set the burner anti-cycling time and confirm by pressing
.
T
Flow
(tar-
get)
[°C]
Set maximum burner anti-cycling time [min]
1
5
10
15
20
25
30
30
2.0
4.0
8.5 12.5 16.5 20.5 25.0
35
2.0
4.0
7.5 11.0 15.0 18.5 22.0
40
2.0
3.5
6.5 10.0 13.0 16.5 19.5
45
2.0
3.0
6.0
8.5 11.5 14.0 17.0
50
2.0
3.0
5.0
7.5
9.5 12.0 14.0
55
2.0
2.5
4.5
6.0
8.0 10.0 11.5
60
2.0
2.0
3.5
5.0
6.0
7.5
9.0
65
2.0
1.5
2.5
3.5
4.5
5.5
6.5
70
2.0
1.5
2.0
2.5
2.5
3.0
3.5
75
2.0
1.0
1.0
1.0
1.0
1.0
1.0
T
Flow
(target)
[°C]
Set maximum burner anti-cycling time
[min]
35
40
45
50
55
60
30
29.0
33.0
37.0
41.0
45.0
49.5
35
25.5
29.5
33.0
36.5
40.5
44.0
40
22.5
26.0
29.0
32.0
35.5
38.5
45
19.5
22.5
25.0
27.5
30.5
33.0
50
16.5
18.5
21.0
23.5
25.5
28.0
55
13.5
15.0
17.0
19.0
20.5
22.5
60
10.5
11.5
13.0
14.5
15.5
17.0
65
7.0
8.0
9.0
10.0
11.0
11.5
70
4.0
4.5
5.0
5.5
6.0
6.5
75
1.0
1.0
1.0
1.0
1.0
1.0
8.1.2
Resetting the remaining burner anti-cycling
time
▶
Press
.
8.2
Setting the pump output
The product is equipped with a speed-regulated high-effi-
ciency pump, which adjusts independently to the hydraulic
conditions of the heating installation.
If you have installed a low loss header in the heating install-
ation, you should switch off the speed regulation and set the
pump output to a fixed value.
▶
If required, change the setting of the pump speed, which
depends on the operating mode, under diagnostics code
d.14
.
Overview of diagnostics codes (
8.2.1
Pump diagram
0
50
100
150
200
250
300
350
0
200
400
600
800
1000
1200
A
B
1
2
A
Remaining feed head
[mbar]
B
Flow rate [l/h]
1
Max. PWM
2
Min. PWM
8.3
Setting the bypass valve
Caution.
Risk of material damage caused by incor-
rect setting of the high-efficiency pump
If the pressure at the bypass valve is in-
creased (by turning it clockwise) and the
pump output is set to less than 100%, the
product may not operate correctly.
▶
In this case, set the pump output to
5 = 100% using diagnostics parameter
d.14
.
Condition
:
d.14
is set to 0 = auto
▶
Do not change the factory settings.
Condition
:
d.14
is set to 1 - 5
▶
Remove the front casing. (