![Vaillant ecoFIT sustain 825 Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/vaillant/ecofit-sustain-825/ecofit-sustain-825_installation-and-maintenance-instructions-manual_4100072019.webp)
Start-up 7
0020230529_04 ecoFIT sustain Installation and maintenance instructions
19
7.11.2 Checking the air/flue pipe/flue gas
recirculation
1.
Check the flue gas installation is intact in accordance
with the latest gas safe technical bulletin and informa-
tion supplied in the installation instructions.
2.
For extended flue gas installations check for flue gas
recirculation using the air analysis point.
3.
Use a flue gas analyser.
4.
If you discover CO or CO
2
in the supply air, search for
the leak in the flue system or for signs of flue gas recir-
culation.
5.
Eliminate the damage properly.
6.
Check again whether the supply air contains any CO or
CO
2
.
7.
If you cannot eliminate the damage, do not start up the
product.
7.11.3 Thoroughly flushing the heating installation
("hot")
1.
Operate the appliance until the boiler and the heating
system are up to temperature.
2.
Check the heating system for leaks.
3.
Connect a hose to the drain valve located at the lowest
position of the heating system.
4.
Shut off the boiler, open the drain valve and all purge
valves on the radiators and allow the water to flow out
of the heating system and the boiler quickly and fully.
5.
Close the drain valve.
6.
Fill and purge the heating installation. (
7.
Re-fill the system until the system design pressure of
0,1 MPa (1,0 bar) is attained.
Note
The actual reading on the digital pressure
gauge should ideally be 0,05 MPa (0,5 bar)
plus an additional pressure corresponding
to the highest point of the system above the
base of the boiler
–
10 m head equals an ad-
ditional 1 bar reading on the pressure gauge.
The minimum pressure should not be less
than 0,1 MPa (1 bar) in any installation. If
the system is to be treated with an inhibitor it
should be applied at this stage in accordance
with the manufacturer’s instructions. Further
information can be obtained from Sentinel,
Betz Dearborn Ltd., Tel: 0151 420 9595, or
Fernox, Alpha
–
Fry technologies. Tel: 0870
8700362.
8.
Install the front casing. (
7.11.4 Checking the CO
₂
content
1.
Start up the product with check programme
(P.01)
.
2.
Wait until the value that is read is stable.
–
Waiting period for reading a stable value: 5 min
1
3.
Unscrew the cover from the flue gas analysis point
(1)
.
4.
Measure the CO
₂
content at the flue gas analysis point
(1)
.
5.
Compare the measured value with the corresponding
value in the table.
Checking the CO
₂
content
Great Britain
front casing on / front casing off
Natural gas
G20
9.2
±
1 %
◁
The value is OK.
▽
The value is not OK; you cannot start up the
product.
▶
Inform Customer Service.
7.12
Checking leak-tightness
▶
Check the gas pipe, the heating circuit and the hot water
circuit for leak-tightness.
▶
Check that the air/flue pipe has been installed correctly.
Condition
: Room-sealed operation
▶
Check whether the vacuum chamber has been closed
tightly.
7.12.1 Checking the heating mode
1.
Activate the heating mode on the user interface.
2.
Turn all thermostatic radiator valves on the radiators
until they are fully open.
3.
Allow the product to operate for at least 15 minutes.
4.
Fill and purge the heating installation. (
5.
Call up the status codes. (
Status codes
–
Overview (
◁
If the product is working correctly, the display shows
S.04
.
7.12.2 Checking the hot water generation
1.
Activate the hot water handling mode on the user
interface.
2.
Open a hot water valve completely.
3.
Call up the status codes. (
Status codes
–
Overview (
◁
If the product is working correctly, the display shows
S.14
.