background image

X

5

OPT

01 115

 VAC / Encoder Interface Option Board

vacon 

 

5

Email: [email protected]  •  Fax 717-264-3115 

Figure 1:  Option Board Layout

Before you can install the option board, you must first remove the drive cover. 

Figure 2 shows the locations of the cover screws.  The torque range for the X5 Size 1 cover is 18-26 in/lbs. 

Figure 2:  Cover Assembly and Screw Locations

Encoder / 115 VAC Interface 

Control Relay Terminals

Encoder Interface Power 

Supply Selector

Cover screw locations

Cover screw locations

Содержание X5OPT01

Страница 1: ...X5OPT01 115 VAC Encoder Interface Option Board Installation Manual DPD00113 ...

Страница 2: ...Vacon Inc Chambersburg PA 17202 Normal business hours North America 8 00 AM to 5 00 PM Eastern time 1 877 Vacon06 1 877 822 6606 After hours support is also available and Vacon Inc are trademarks of Vacon Plc a member of Vacon Group All other product names are trademarks of their respective companies Copyright 2009 Vacon Incorporated All rights reserved ...

Страница 3: ...ive functions With this option an encoder with a nominal rating of up to 2048 pulses per revolution can be connected to the X5 unit to improve speed load regulation of the drive Overall encoder frequency at maximum process speed must be limited to 100kHz This option also provides two additional control relays each rated for 115 VAC 1 amp or for 230 VAC 0 5 amp Applicable Documents This manual is s...

Страница 4: ... discharge Ensure that any other power sources that may feed control logic have been disconnected DO NOT short across DC bus capacitors or touch unshielded components or terminal strip screw connections with voltage present Install all covers before applying power or starting and stopping the drive The user is responsible for conforming to all applicable code requirements with respect to grounding...

Страница 5: ...all the option board you must first remove the drive cover Figure 2 shows the locations of the cover screws The torque range for the X5 Size 1 cover is 18 26 in lbs Figure 2 Cover Assembly and Screw Locations Encoder 115 VAC Interface Control Relay Terminals Encoder Interface Power Supply Selector Cover screw locations Cover screw locations ...

Страница 6: ...g Locations Once the board is in place tighten the screws to a maximum of 26 in lbs Next install the flexible circuit to finish the interface to the control board Refer to Figure 4 on page 6 To install the flexible circuit first remove the keypad frame necessary in this size unit The frame is attached with two screws in opposite corners the screws thread into fasteners in the plastic assembly Afte...

Страница 7: ... 708 Terminal NO4 is a normally open contact it will close when the relay activates NC4 is a normally closed contact it will open when the relay activates RC4 is the common terminal associated with both contacts The ratings of these contacts are 115 VAC 1 amp and 230 VAC 0 5 amp A A Channel A input from the encoder Compatible with line driver open collector or totem pole outputs from an encoder If...

Страница 8: ...e wound media but as the diameter of the media on the spool changes the motor turning the spool needs to vary its speed to maintain the linear speed at the idler pulley When parameter 224 is set to 0 it is ignored and the PID calculates the feedback percentage based on parameter 301 Maximum Frequency When this parameter is set to a non zero value the PID uses instead Parameter 224 s setting to cal...

Страница 9: ...d calibration of the Vmet and Imet outputs both have selections related to the status of the encoder input The Program Sequencer function can also key off the encoder s home pulse To make use of this function the encoder s home pulse 1 pulse per revolution must be connected to the C input of the encoder board Troubleshooting Any problem with the encoder interface will result in an F37 fault Four a...

Страница 10: ...ne 47 330 96120 fax 47 330 96130 romania Vacon Romania Reprezentanta Cuza Voda 1 400107 Cluj Napoca Tel 40 364 118 981 Fax 40 364 118 981 russia ZAO Vacon Drives Ul Letchika Babushkina 1 Stroenie 3 129344 Moscow telephone 7 495 363 19 85 fax 7 495 363 19 86 ZAO Vacon Drives 2ya Sovetskaya 7 office 210A 191036 St Petersburg telephone 7 812 332 1114 fax 7 812 279 9053 slovakia Vacon s r o Branch Seb...

Отзывы: