X5 AC Drive User’s Manual
Chapter 7: X5 Parameters
DPD00089A
-
71 -
© 2009 Vacon Incorporated All Rights Reserved
7.3
Description of Parameters
Table 7-2 lists the X5 parameters in the order in which they appear in the keypad display. For each
parameter, the table lists the default value and range and also describes the use of the parameter.
Table 7-2: Description of X5 Parameters
(Page 1 of 40)
001 Model Number
Read-Only
Range: n/a
Level: 1,2
Parameter
001
, the
Model Number
parameter, contains the portion of the X5 model number related to voltage and
horsepower. The number format is
vvhhf
, where
vv
is the code for the input voltage (20=230 Vac, three-phase; 40=460
Vac, three-phase; 50=575 Vac, three-phase);
hh
is horsepower; and
f
is the fractional part of the horsepower. Example:
20050
= 230 Vac, three-phase, 5.0 HP model.
002 Software Rev
Read-Only
Range: 0.00-99.99
Level: 2
Parameter
002,
the
Software Revision
parameter, displays the software revision that is installed in the drive.
Options:
0.00-99.99
003 Rated Current
Read-Only
Range: 0.0-200.0 A
Level: 2
Parameter
003,
the
Rated Current
parameter, displays the normal duty current rating of the model of drive.
005 Serial No 1
Read-Only
Range: 0-65535
Level: 2
Parameter
005,
Serial No 1
, contains a number that corresponds to the year and week in which the drive was
manufactured. The data in this parameter and parameter 006 are combined to make the drive serial number.
006 Serial No 2
Read-Only
Range: 0-65535
Level: 2
Parameter
006, Serial No 2
, contains a number that determines the number of the drive that was manufactured during
the week of Serial No 1. The data in this parameter and parameter 005 are combined to make the drive serial number.
007 USB Soft. Rev
Read-Only
Range: n/a
Level: 2
Parameter
007, USB Soft. Rev
, shows the revision of the USB software resident in the drive.
For more information on using the USB interface, and saving drive parameters and Keeper data to a USB flash memory
device, see
“Storing Data and Reflashing Using a Flash Memory Device” on page 52
.
008 Option Installed
Read-Only
Range: n/a
Level: 2
This parameter identifies the option installed in the drive. Options are:
Value
Description
0
No options installed
1
X5OPT01
2
X5DNET01
3
X5EIP01
4
X5PROFI01
5
X5RS48501
7
X5MBTCP01
009 Fbus Soft. Rev
Read-Only
Range: n/a
Level: 2
This parameter shows the revision level of the Fieldbus software in the option board attached to the drive.
030 Pwr Down Date
Read-Only
Range: n/a
Level: 2
This parameter shows the date of last power-down or reset of the drive, in dd/mm/yy format.