Commissioning
vacon • 57
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
6
6.
C
OMMISSIONING
Danfoss provides samples of function blocks and add-on-instructions to support commissioning of
drive fieldbus interfaces. They are published with source code. For more information, visit
www.danfoss.com
.
The OPTEA and OPTE9 option boards can be commissioned with the control keypad by giving values
to appropriate parameters in the option board menu (or via PC tools, see Chapter 5.8 "PC Tools").
Keypad commissioning procedures and location of parameters differ a little with different AC drive
types:
•
In the VACON
®
NXP/NXS option board, parameters are located under the menu M5
(Expander board menu).
•
In the VACON
®
100 family option board, parameters are located under the menu M7 (I/O and
Hardware).
6.1
Option board menu
The control keypad makes it possible for the user to see which expander boards are connected to
the control board and to reach and edit the parameters associated with the expander board.
6.1.1
Option board parameters
The table below contains panel parameters for OPTEA and OPTE9 boards. Basic parameters are
identical but the Advanced Dual Port Ethernet board (OPTEA) has special settings.
Notice that the table below lists parameters with latest option board firmware. Older firmware
versions may not contain all parameters listed here.
Table 15. Parameters menu structure
Name
Default
Range
Description
Comm. Protocol*
Modbus
None (0),
Modbus (1),
Profinet IO (2),
EtherNet/IP (3)
Active protocol. If "None" is selected, then
there is no active fieldbus protocol in
option board.
Comm. Timeout
10 s
0…65535 s
Communication timeout in seconds. For
PROFINET IO and EtherNet/IP it is recom-
mended to use zero value.
Mode*
Normal
Normal (1),
NX Mode (2),
V100 Mode (3)
Normal (1),
OPTCx Mode (2)
Only when installed to VACON
®
100 family.
After this setting is changed, drive must be
restarted.
Only in OPTEA and when installed to
VACON
®
NXP family. After this setting is
changed, drive must be restarted.
Sub menu: IP Settings
IP Address Mode*
DHCP
Fixed IP (1),
DHCP (2),
DCP (3)
IP Part 1*
192
1…223
IP Address Part 1
IP Part 2*
168
0…255
IP Address Part 2
IP Part 3*
0
0…255
IP Address Part 3
IP Part 4*
10
0…255
IP Address Part 4