6 • vacon

 

 

 

technical data

 

Tel: +358-201-2121 • Fax: +358-201-212 205 

converters. Attention should be paid to proper grounding of the shield to ensure bus 

operation. Grounding of the shield should be done at both ends of the cable. 

 

   

  Cable type 

Max. doubly  

terminated  

bus length 

Max. free  

topology 

wire length 

Max. node-to-node 

distance 

Belden 85102 (unshielded) 

2700 m 

500 m 

500 m 

Belden 8471 
LONAK 2x1,3 (unshielded) 

2700 m 

500 m 

400 m 

Level IV, 22AWG  
LONAK 2x2x0,65 (unshielded) 

1400 m 

500 m 

400 m 

JY (St) Y 2x2x0.8mm  
LONAK 2x2x0,8 (shielded) 

900 m 

500 m 

320 m 

Table 2-2. Line length for different transmission speeds 

 

2.3

 

Profiles 

LonMark Functional Profiles describe in detail the application layer interface, including the network 

variables, configuration properties, and default and power-up behaviors required on LonMark devices 

for specific, commonly used control functions. 

 

2.3.1

 

Variable Speed Drive Profile 

Leading manufacturers of drive technology have jointly defined the LonMark profile. The profile 

specifies how the drives are to be parameterized and how the setpoints and actual values are to be 

transmitted. This enables drives from different vendors to be exchanged. The profile contains 

necessary specifications for speed control and positioning. It specifies the basic drive functions while 

leaving sufficient freedom for application-specific expansions and further developments. 

 

 

 

Содержание OPTC4

Страница 1: ...vacon nx ac drives optc4 lonworks option board user manual...

Страница 2: ...2 Grounding of bus cable shield in OPT C4 8 3 3 Bus termination resistors 10 3 4 LED indications 10 4 INSTALLATION OF VACON NX LonWorks BOARD 12 4 1 Board information sticker 14 5 COMMISSIONING 15 5 1...

Страница 3: ...es on a network communicate with each other using LonTalk protocol Interoperable nodes use Standard Network Variable Types SNVT for communicating over the network The definition of an SNVT includes un...

Страница 4: ...Pluggable connector 5 mm Communications Channel type TP FT 10 Transfer cable Twisted pair Baud rate 78 Kbit s Environment Ambient operating temperature 10 C 50 C Storing temperature 40 C 70 C Humidit...

Страница 5: ...Echelon s LPT 10 Link Power Transceiver and these transceivers can communicate with each other on a single twisted pair cable termination termination Figure 2 1 Doubly Terminated Bus Topology termina...

Страница 6: ...sion speeds 2 3 Profiles LonMark Functional Profiles describe in detail the application layer interface including the network variables configuration properties and default and power up behaviors requ...

Страница 7: ...d to the fieldbus through 3 pin pluggable bus connector The communication with the control board takes place through the standard Vacon Interface Board Connector 3 1 LonWorks OPT C4 option board Figur...

Страница 8: ...talled in slot E of the control board It is not necessary to detach the whole board for the grounding of the bus cable shield Just detach the terminal block 3 2 1 Grounding the bus cable shield direct...

Страница 9: ...he data cables and the shield in their respective terminals See Table 3 1 Figure 3 5 4 If the LonWorks board was detached from the control unit place it into slot E of the control board see board inst...

Страница 10: ...t be set accordingly Use 94 ohm termination resistance when only one termination is needed and 47 ohm for two terminations Figure 3 7 Using jumper X5 to set the bus termination 3 4 LED indications The...

Страница 11: ...is ready for external communication Blinking slow once 5 s Option board is activated and in FAULT state Internal fault on option board Bus status LED H1 GREEN LED is Meaning OFF Fieldbus module is wai...

Страница 12: ...205 4 4 INSTALLATION OF VACON NX LONWORKS BOARD NOTE MAKE SURE THAT THE FREQUENCY CONVERTER IS SWITCHED OFF BEFORE AN OPTION OR FIELDBUS BOARD IS CHANGED OR ADDED A Vacon NX frequency converter B Remo...

Страница 13: ...d in slot E on the control board of the frequency converter Make sure that the grounding plate see below fits tightly in the clamp 21 22 23 H3 H2 H1 X5 lw1 fh8 E Make a sufficiently wide opening for y...

Страница 14: ...livered by the factory includes a sticker shown below Please mark the board type 1 the slot into which the board is mounted 2 and the mounting date 3 on the sticker Finally attach the sticker on your...

Страница 15: ...ntrol board and 2 to reach and edit the parameters associated with the expander board Enter the following menu level G with the Menu button right At this level you can browse through slots A to E with...

Страница 16: ...for the active control place see Vacon NX User s Manual Chapter 7 3 3 Master software 1 Write 100 0 1 to nviDrvSpeedStpt 2 Frequency converter status is RUN and output frequency is 1 00 nviDrvSpeedSc...

Страница 17: ...Direct control of Vacon NX e g Run Stop Direction Speed reference Fault reset Full access to all Vacon NX parameters Monitor Vacon NX status e g Output frequency Output current Fault code 6 1 General...

Страница 18: ...IN5 SNVT_lev_percent nv15 nviProcessIN6 SNVT_lev_percent nv16 nviProcessIN7 SNVT_lev_percent nv17 nviProcessIN8 SNVT_lev_percent nv31 nvoProcessOut2 SNVT_lev_percent nv32 nvoProcessOut3 SNVT_lev_perce...

Страница 19: ...the Node object or the Variable Speed Motor Drive object within a node Supported requests are RQ_NORMAL RQ_UPDATE_STATUS RQ_CLEAR_STATUS RQ_REPORT_MASK RQ_DISABLED RQ_ENABLE and RQ_CLEAR_ALARM nviDrv...

Страница 20: ...able provides a mechanism to clear the kWh trip counter or the Drive total running hours trip counter 1 MWh trip counter 2 Operation day trip counter nviProcessIn1 8 These input network variables are...

Страница 21: ...98 Actual Values 99 Active Fault Code 100 Not Used 101 899 Parameter 900 999 Reserved Reserved for LonWorks board internal usage 1000 Not Used 1001 1999 Parameter Table 6 5 Grouping of ID numbers Exam...

Страница 22: ...hour 0 h 65535 Status word nvoDrvStatus SNVT_state n a n a kWh trip counter nvoDrvEnrgy SNVT_elect_kwh 0kWh 65535kWh Active fault code nvoActFault SNVT_count 0 41 Process Out nvoProcessOut1 8 SNVT_ le...

Страница 23: ...Description Value 0 Value 1 0 Not Ready Ready 1 FC stopped Running 2 Clockwise Counterclockwise 3 No fault Fault active 4 No warning Warning active 5 Reference Actual value Reference Actual value Tabl...

Страница 24: ...DigitalOut1 8 These output network variables are sent directly from the application see more detailed explanation in chapter 6 5 Process data state value command 0 0 off 0 0 1 200 0xC8 on 200 1 1 0XfF...

Страница 25: ...as a percentage of nominal speed in RPM as defined by the Nominal Speed nciNmlSpeed configuration value The value of the maximum speed must be validated against the value of the minimum speed as foll...

Страница 26: ...rties nciMinSpeed nciMaxSpeed entered as a percentage of nominal speed nciNmlFreq This configuration property is used to provide the nominal frequency for the motor nciRampUpTm Defines the acceleratio...

Страница 27: ...bit 4 bit 5 bit 6 bit 7 bit 10 bit 11 bit 12 nviDigitaln 2 nviDigitaln 3 nviDigitaln 4 nviDigitaln 5 nviDigitaln 6 nviDigitaln 7 nviDigitaln 8 bit 1 FBGeneralStatusWord bit 2 bit 3 bit 4 bit 5 bit 6...

Страница 28: ...3 Fieldbus fault The received heartbeat time has expired Check the installation If installation is correct contact the nearest Vacon distributor 54 Slot fault Defective option board or slot Check the...

Страница 29: ...T 6 Motor Voltage V 0 1 V Process data OUT 7 DC link voltage V 1 V Process data OUT 8 Active Fault Code The Multipurpose Control Application has a selector parameter for every Process Data The monitor...

Страница 30: ...5 7 PID control and Pump and fan control applications Data Value Unit Step Process Data IN1 Reference for PID controller 0 01 Process Data IN2 Actual Value 1 to PID controller 0 01 Process Data IN3 Ac...

Страница 31: ......

Страница 32: ...D Rev A Manual authoring documentation vacon com Vacon Plc Runsorintie 7 65380 Vaasa Finland Subject to change without prior notice 2012 Vacon Plc Find your nearest Vacon office on the Internet at www...