Fault codes
vacon • 21
24-hour s358 (0)40 8371 150 • Email: [email protected]
6.
FAULT CODES
The fault codes, their causes and correcting actions are presented in the table below. The shadowed
faults are A faults only. The items written in white on black background present faults for which you
can program different responses in the application. See parameter group Protections.
Note: When contacting distributor or factory because of a fault condition, always write down all texts
and codes on the keypad display.
Fault
code
Fault
Possible cause
Correcting measures
1
Overcurrent
BCU has detected too high current
(>4*I
H
) in the resistor cables:
- Check cables.
- Check resistors
2
Overvoltage
The DC-link voltage has exceeded the
limit:
911V for 500V BCU
1200V for 690V BCU
7
Saturation trip
Various causes:
−
defective component
−
brake resistor short-circuit or
overload
- Cannot be reset from the keypad.
- Switch off power.
- DO NOT RE-CONNECT POWER!
- Contact your local distributor.
8
System fault
-
component failure
-
faulty operation
Note exceptional fault data record
Subcode in T.14:
S1 = Reserved
S2 = Reserved
S3 = Reserved
S4 = Reserved
S5 = Reserved
S6 = Reserved
S7 = Charging switch
S8 = No power to driver card
S9 = Power unit communication (TX)
S10 = Power unit communication (Trip)
S11 = Power unit comm. (Measurement)
Reset the fault and restart.
Should the fault re-occur, contact your
local distributor. Please visit:
http://www.vacon.com/wwcontacts.html
9
Undervoltage
DC-link voltage is under the BCU fault
voltage limit:
333VDC for 500V BCU
460VDC for 690V BCU
−
most probable cause: too low
supply voltage in the system
−
BCU internal fault
- In case of temporary supply voltage
break, reset the fault and restart the
frequency converter.
- Check the supply voltage.
- If it is adequate, an internal failure has
occurred.
- Contact your local distributor.
Please visit:
http://www.vacon.com/wwcontacts.html
13
BCU under-
temperature
Heatsink temperature is under –10
°
C
14
BCU over-
temperature
Heatsink temperature is over 90
°
C
Overtemperature warning is issued
when the heatsink temperature exceeds
85
°
C.
- Check the correct amount and flow of
cooling air.
- Check the heatsink for dust.
- Check the ambient temperature.