11
vacon • 102
FAULT TRACING
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
11.
FAULT TRACING
The fault codes, their causes and correcting actions are presented in Table 37 below. The converter
has an internal memory for storing the converter status at the time of fault as well as additional
information about the source of the fault. This feature is intended to help the user or the service
personnel to determine the cause of fault.
11.1
Fault time data record
When a fault occurs a fault code is displayed on the keypad. By pushing the
Menu button right
here
you will enter the
Fault time data record menu
indicated by T.1
T.16. In this menu, some selected
important data valid at the time of the fault are recorded.
Table 36. Fault time recorded data
T.1 Operation days
D
T.2 Operation hours
hh:mm:ss
T.3 Output frequency
Hz
T.4 Motor current
A
T.5 Motor voltage
V
T.6 Motor power
%
T.7 Motor torque
%
T.8 DC voltage
V
T.9 Unit temperature
°
C
T.10 Run status
T.11 Direction
T.12 Warnings
T.13 0-speed*
T.14
Subcode.
Contains more specific information about the fault.
S1…S#:
A1:
System generated fault. See fault table below.
Application generated fault. See table below or application-
specific mentation
T.15
Module code
.
Indicates where the fault was detected.
Power:
Power1:
Power2:
Control:
Expander:
Adapter:
Starcoupler:
Motor:
Software:
Power unit of the converter (sizes up to FR11)
First power unit in a parallel converter (e.g. in FR12)
Second power unit in a parallel converter (e.g. in FR12)
Control part or control part communication
Expander board or expander board communication
Adapter board or adapter board communication
Starcoupler board (parallel unit only, e.g. FR12)
Motor-related problem
Application software
Содержание nxp/c
Страница 1: ...vacon nxp c ac drives user manual ...
Страница 2: ......
Страница 110: ......
Страница 111: ......